Trane Tracer ZN.520 Manual page 93

Unit controller
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

Step
Fan
J1-1
1
Off
1: Off
2
High
2: Fan high
3
Off
3: Fan med
4
Off
4: Fan low
5: Main open, DX on High
6: Main close, DX
High
off, aux open
7: Aux open, exhaust
High
5
fan
8: Aux close, damper
High
open
9: Outdoor air
High
damper close
10: Generic/
High
baseboard heat
energized
6
11: Exit
The controller automatically exits the
manual test mode after one hour and
reverts back to normal operation.
CNT-SVX04A-EN
Troubleshooting
Table 59 Test sequence for face/bypass unit configurations
DX, or cool
or heat/cool
changeover
valve
J1-2
J1-3
J1-5
J1-6
Off
Off
Off
NA
Off
Off
Off
NA
Med
Off
Off
NA
Off
Low
Off
NA
Off
Off
On
NA
Off
Off
Off
NA
Exh
Off
Off
NA
Off
Off
Off
NA
Off
Off
Off
NA
Off
Off
Off
NA
1
Note
: Upon entering manual output test mode, the controller turns off all fan outputs and drives all
dampers and valves closed (if required).
2
Note
: At the beginning of step 2, the controller attempts to clear all diagnostics.
3
Note
: If the unit is configured for a 2-speed fan, the fan remains on high speed at step 3.
4
Note
: If the unit is configured for a 2-speed fan, the low fan speed output engergizes at step 3. If the
unit is configured for a 1-speed fan, the fan remains on high speed at step 3.
5
Note
: If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The
exhaust fan output is shared with medium fan speed.
6
Note
: After step 10, the test sequence performs an exit. This initiates a reset and attempts to return
the controller to normal operation.
Minimum timers
The outputs are not subject to minimum times during the test sequence.
However, the test sequence only permits one step per second, which enforces a
minimum output time.
LED operation
The green status LED is off when you press the Test button. To begin the
manual output test mode, press and hold the Test button (which causes the
green LED to go off) for at least two seconds, then release the button. The green
LED blinks, indicating the controller is in manual test mode.
Face/ bypass
Electric heat,
damper
or heat valve
J1-7
J1-8
J1-9
J1-10
Off
On
Off
NA
On
Off
Off
NA
On
Off
Off
NA
On
Off
Off
NA
On
Off
Off
NA
On
Off
On
NA
On
Off
On
NA
Off
On
Off
NA
Off
On
Off
NA
Off
On
Off
NA
Generic/
Outdoor air
baseboard
damper
heat
J1-11
J1-12
TB4-1
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
Off
Off
Off
On
91