Trane Tracer ZN.520 Manual page 84

Unit controller
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

82
Configuration
Table 50 Discharge air limits
Configuration
1
Low limit
2
Control point high limit
2
Control point low limit
1
Note
: The low limit is the temperature at which the controller shuts down the unit to prevent the coil
from freezing.
2
Note
: The control algorithm is limited to calculating this discharge air temperature.
Table 51 Freeze avoidance
Configuration
Freeze avoidance setpoint
Table 52 Occupied bypass timer
Configuration
1
Occupancy bypass timer
1
Note
: The occupied bypass timer is used for timed override applications when a building automation
system is not present or when the building automation system does not send the occupied (override)
request. The timed override timer is maintained in the unit controller. When the timed override is
applicable, the controller reports Occupied Bypass as its effective occupancy mode. (The actual
enumeration of nvoEffectOccup is OC_BYPASS during the override condition.)
Table 53 Power-up control wait
Configuration
Power up control wait (2 minutes)
Table 54 Maintenance timers
Configuration
Maintenance timer
Valid range
30–50 ° F
38–150 ° F
35–150 ° F
Valid range
20 to 60 ° F
Valid range
0–240 minutes
(1 minute resolution)
Valid range
Disable or enable
Valid range
0–10,000 hours
CNT-SVX04A-EN