18
Binary outputs
Table 10 Two-pipe cooling valve control with electric heat (1- or 2-stage)
J1-1
Fan high
J1-2
Fan medium/Exhaust fan
J1-3
Fan low
J1-4
(Key)
J1-5
Cool—open
J1-6
Cool—close
J1-7
Not used
J1-8
Not used
J1-9
Electric heat—stage 1
J1-10
Electric heat—stage 2
J1-11
Outdoor air damper—open
J1-12
Outdoor air damper—close
TB4-1
Generic/Baseboard heat output
TB4-2
24 VAC
Table 11 Two-pipe heat valve control
J1-1
Fan high
J1-2
Fan medium/Exhaust fan
J1-3
Fan low
J1-4
(Key)
J1-5
Not used
J1-6
Not used
J1-7
Not used
J1-8
Not used
J1-9
Heat—open
J1-10
Heat—close
J1-11
Outdoor air damper—open
J1-12
Outdoor air damper—close
TB4-1
Generic/Baseboard heat output
TB4-2
24 VAC