Trane Tracer ZN.520 Manual page 92

Unit controller
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

Step
Fan
J1-1
1
Off
1: Off
High
2
2: Fan high
3
Off
3: Fan med
4
Off
4: Fan low
5: Main open, DX
High
on
6: Main close, DX
High
off, aux open, EH1
on
7: Aux open, EH1
High
5
on, exhaust fan
8: Aux close, EH1
High
off, EH2 on,
damper open
9: Damper close
High
10: Generic/
High
baseboard heat
energized
6
11: Exit
90
Troubleshooting
Table 58 Test sequence for non-face and bypass unit configurations
DX, or cool or
heat/cool
changeover
valve
J1-2
J1-3
J1-5
Off
Off
Off
On
Off
Off
Off
Off
Med
Off
Off
Off
Off
Low
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Exh
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
1
Note
: Upon entering manual output test mode, the controller turns off all fan and electric heat outputs
and drives all dampers and valves closed (if required).
2
Note
: At the beginning of step 2, the controller attempts to clear all diagnostics.
3
Note
: If the unit is configured for a 3-speed fan, the medium fan speed output will energize at step 3.
If the unit is configured for a 2-speed fan, the fan remains on high speed at step 3.
4
Note
: If the unit is configured for a 3-speed fan, the medium fan speed output energizes at step 3. If
the unit is configured for a 2-speed fan, the low fan speed output engergizes at step 3. If the unit is
configured for a 1-speed fan, the fan remains on high speed at step 3.
5
Note
: If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The
exhaust fan output is shared with medium fan speed.
6
Note
: After step 10, the test sequence performs an exit. This initiates a reset and attempts to return
the controller to normal operation.
Face/ bypass
Electric heat, or
damper
heat valve
J1-6
J1-7
J1-8
J1-9
NA
NA
Off
NA
NA
Off
NA
NA
Off
NA
NA
Off
NA
NA
Off
NA
NA
On
NA
NA
On
NA
NA
Off
NA
NA
Off
NA
NA
Off
Outdoor air
damper
J1-10
J1-11
J1-12
Hydronic: on
Off
On
EH: off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
Off
Off
Off
On
Off
Off
Off
Generic/
baseboard
heat
TB4-1
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
CNT-SVX04A-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents