Trane Tracer ZN.520 Manual page 106

Unit controller
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

104
Appendix
Table 70 Unit operation based on the effective heat/cool output (Continued)
Application
Heat/cool
mode input
mode input
(nviApplicMode)
(nviHeatCool)
Heat
Any state
Morning warm up Any state
Cool
Any state
Pre-cool
Any state
Off
Any state
Test
Any state
Fan only
Any state
1
Note
: Use of heat for supply air tempering and dehumidification remains available.
2
Note
: Night purge, Emergency heat, and Null modes are not supported by the Tracer ZN.520 zone
controller. If one of these modes is received by the controller, it is interpreted as Auto.
Effective heat/
Unit operation
cool mode
output
(nvoHeatCool)
Heating
Fan-enabled
Heating-enabled
Cooling-disabled
Damper-enabled
Morning warm
Fan-enabled
up
Heating-enabled
Cooling-disabled
Damper-disabled
Cool
Fan-enabled
Heating-disabled
Cooling-enabled
Damper
Pre-cool
Fan-enabled
Heating-disabled
Cooling-enabled
Damper-disabled
Off
Fan-disabled
Heating-disabled
Cooling-disabled
Damper-disabled
Determined by
Fan-enabled
controller
Heating-enabled
Cooling-enabled
Damper-enabled
Fan only
Fan-enabled
Heating-disabled
Cooling-disabled
Damper-enabled
1
1
CNT-SVX04A-EN