GOOSE
5.3.5
5.3.5.1
30
GUID-DF37270F-6836-4C5D-A883-D8300DD930D1 V1 EN
Figure 14:
Updated address properties for the new GOOSE control block

Configuring a GOOSE subscriber

A 615 series IED application can receive and use single binary, double binary,
integer and floating point values with attached quality information. A quality
attribute is received and processed automatically.

Configuring GOOSE inputs

1.
Open the Project Navigator window.
2.
In the IEC 61850 Data Engineering window on the right, select the Goose
Control Engineering tab.
3.
To configure the GOOSE data connections between the IEDs, drag the data-
receiving IED from Project Navigator submenu to GSE Control.
GUID-03B56D9C-CCF9-4C02-9F67-8B4E377B8DE7 V1 EN
Figure 15:
Dragging the data-receiving IED to GSE Control
The dragged IED is a GOOSE receiver, and all the receiver IEDs are listed in
the Client IED box.
4.
To update the data flow, select Tools/IEC 61850 Data Flow Engineering/
Update DataFlow.
1MRS757255 B