ABB eVD4 Engineering Manual page 34

Breaker integrated protection rbx615
Table of Contents

Advertisement

Section 5
GOOSE
26
GUID-D5AA23C7-F93C-449A-98A2-8E628E4B141E V1 EN
Figure 10:
Creating a data set in CCT600
4.
To add a new data set, click Add in the Data Sets window.
5.
Give the data set an unique name.
To define several data sets under the logical node LLN0, give the data sets
unique names. However, the maximum number of GOOSE control blocks in
a 615 series IED is four. Since one control block uses one data set, the
maximum amount of GOOSE data sets is also four. Usually it is enough to
define one data set and control block for GOOSE service. If the IED sends
also analog values, it is recommended to use a separate data set and control
block for analog values.
After creating the GOOSE data sets, define the data attributes for the data sets.
Defining data attributes
1.
In IEC 61850 Data Engineering window, select the Data Set Engineering
tab.
2.
Select a GOOSE data set.
3.
In the IED Data Model window, select a data attribute to be used and click
Add.
A maximum of 20 data attributes can be added to a single GOOSE data set. If
the configured published data set is larger, it is not accepted by the IED.
1MRS757255 B
Breaker Integrated Protection RBX615
Engineering Guide