Breaker Integrated Protection RBX615
Engineering Guide
615 series data model

615 series implementation

The IEC 61850 communication protocol is always supported by the 615 series
IEDs. If the IED is ordered with no Ethernet communication interface, the front
port on the device still works according to IEC 61850. All settings and
configurations are changed by using IEC 61850 via the front Ethernet port of the
LHMI. Without the Ethernet option, event reporting or peer-to-peer services cannot
be used.
Only one point-to-point connection is allowed to the front port.
This means that no network can be built by using the front port.
The 615 series has been designed to fully support the concepts of IEC 61850. This
means that any information and data offered by the 615 series IEDs can be
modelled according to IEC 61850 and the services for using the data are widely
supported according to the standard.
Process data: monitoring of status information, measurements
Application data: protection activations, tripping, fault recordings
Disturbance recorder files
Control commands
Protection settings
Setting groups
Configuration data
Self-supervision messages
Fast horizontal communication between devices
Time synchronization

Information model

According to the IEC 61850 model, a 615 series IED consists of three logical devices.
Control logical device, CTRL
Disturbance recorder logical device, DR
Protection logical device, LD0
Generic functionality, such as physical inputs and outputs as well as the alarming
LED functionality, resides under LD0.
Section 4
615 series data model
15