ABB eVD4 Engineering Manual page 47

Breaker integrated protection rbx615
Table of Contents

Advertisement

1MRS757255 B
Breaker Integrated Protection RBX615
Engineering Guide
Table 6:
Diagnostics data objects
Data object
Description
Intln1
Received messages
Intln2
Transmitted messages
Intln3
Received state changes
Intln4
Received sequence
number
Intln5
Received frames with
test bit
Intln6
State or sequence
number errors
Intln7
Receiver time-outs
Intln8
Received ConfRev
mismatches
Intln9
Received frames with
Needs Commissioning
Intln10
Errors in received data
set
Alm
Receiver alarm
GOOSE Alarm is activated in the receiver IED in certain situations.
Time-out
Configuration revision mismatch
Error in the received data set
The Needs Commissioning bit is active in the received message
Diagnostics information
When increasing, the IED is receiving GOOSE messages.
When increasing, the IED is sending GOOSE messages.
Received GOOSE messages with a new stNum value.
Received GOOSE retransmissions or heartbeat cycle
messages with a new sequence number.
Received GOOSE frames with the test flag on.
Number of notified sequence number jumps.
Number of notified peer IED time-outs.
When increasing, there is a mismatch between the
received GOOSE frame information and the used GOOSE
configuration.
One peer IED Indicates that its configuration is not valid or
up-to-date.
Received data are syntactically wrong, or there are less
data in received data set than expected.
Alarm signal value connected to the event and application
logic. It is active when one peer IED is in time-out.
Section 5