Section 4
615 series data model
4.3
16
Different configurations have different data models.
During system engineering in the system configuration tool, do not
delete or rename logical devices, logical nodes, data objects or data
attributes in IEC 61850 data model.
GUID-42167015-6E8C-4707-8E3C-5CCB30BE2BF4 V1 EN
Figure 3:
Example of an IEC 61850 data model of a 615 series IED
All definitions for the IEC 61850 communication configuration, such as data sets,
report control blocks, GOOSE control blocks and the setting group control block,
are always located under LD0.LLN0. The full data model is found in the SCL file,
which can be exported from PCM600.

Vertical and horizontal communication

The 615 series IEDs can communicate by using the monitoring and control services
offered by IEC 61850. A client can read and write data, receive either buffered or
1MRS757255 B