5.3.6.3
Breaker Integrated Protection RBX615
Engineering Guide
GUID-534860DB-532D-4941-BDB4-154F1C732D00 V1 EN
Figure 22:
SCL import options in PCM600
6.
Click Import.
For more information, see PCM600 documentation.

Connecting GOOSE inputs to an IED application

1.
In PCM600, open the Project Explorer and select the Plant Structure tab.
2.
Add the GOOSERCV function block by using Application Configuration Tool.
The GOOSERCV function block can only be added by using
Application Configuration Tool.