Figure 13:
Defining GOOSE control block address
The IEC 61850 GSE Applications dialog box shows all the GOOSE control
blocks of the active project. In this dialog box, all the GOOSE control block
addresses in a project can be edited, and it can be ensured that several
GOOSE control blocks are not using the same addresses.
The multicast MAC address is usually unique, and APPID
must be unique.
3.
To configure a new addressing scheme for a new GOOSE control block, click
GSE Application in the IEC 61850 GSE Applications dialog box.
4.
Check the address values.
Table 5:
Address value description
Address value
APPID
MAC Address
VLAN ID
VLAN Prio
MinTime
MaxTime
Description
The application identifier must be a unique HEX value for sending the
GoCB within the system. It identifies the purpose of this particular
data set.
The value range is 0000...3FFF.
A multicast MAC address to which the specific GOOSE data is sent.
The receiving IED filters the frames and starts to process them if a
specific multicast address is defined in the configuration. It is
recommended to have one unique multicast address per GoCB.
The address range for GOOSE Multicast addresses is 01-0C-CD-01-
00-00...01-0C-CD-01-01-FF.
The VLAN identifier can be used if the Ethernet switches in a station
bus support VLAN. If static VLAN IDs are defined, it affects also to
switch port configuration. The value 000 means a non-configured
VLAN and switches do not filter these messages in port basis. This
value is recommended value if there is no need to split logical network.
The VLAN identifier is a 3-character HEX value with range 000...FFF.
The VLAN priority properties can be used in the networks supporting
VLANs. The priority is used with network switches.
The default value for GOOSE is 4 and the value range is 0...7.
With the 615 series IEDs, only the MaxTime is
configurable.
The MinTime indicates the maximum response time in milliseconds to
data change. This time can be used by the receiver to discard
messages that are too old. In principle, the MinTime can vary
depending on the data type, but for the 615 series IEDs, the value is
always 10 ms for sent data.
The MaxTime indicates the background "heartbeat" cycle time in
milliseconds; the default value is 10 000 ms. If there are no data
changes, the IED still resends the message with the heartbeat cycle
to enable the receiver to detect communication losses, that is, the
communication is supervised.