Hayward ENERGYLINE INVERTER Series Installation & Operation Manual page 32

Swimming pool/spa heat pump unit
Table of Contents

Advertisement

7.1 Error Codes
Problem
Water inlet sensor fault
Water outlet sensor fault
Outside temperature sensor fault
De-icing sensor fault
Compressor aspiration sensor defect
Compressor discharge sensor fault
High pressure protection
Low pressure protection
Flow sensor fault
Input/Output temperature difference
> 13°C
Antifreeze protection Cooling mode
Communication problem
Level 1 antifreeze protection
Level 2 antifreeze protection
Fan motor fault
Fan motor fault
Exterior temperature too low
Page 32
7. TROUBLESHOOTING
Error
Description
codes
P01
P02
P04
The sensor is open or has
short-circuited.
P05
P07
P081
The sensor is open or has short-
E01
circuited.
The sensor is open or has short-
E02
circuited.
The sensor is open or has short-
E03
circuited.
E06
Applicable in Cooling mode only
E07
Water output temperature < 4°C
No communication between the parent
E08
electronic card and the Inverter card
2°< Water temperature < 4°
E19
and Air temperature < 0°
Water temperature < 2°
E29
and Air temperature < 0°
F031
Motor jammed or faulty conntection
F051
Faulty connection
TP
Operating limit reached
USE ONLY HAYWARD® GENUINE REPLACEMENT PARTS
Solution
Check the CN21/RES1 connections on the PCB or replace the sensor
Check the N22/RES2 connections on the PCB or replace the sensor
Check the CN12/PH connections on the PCB or replace the sensor
Check the CN8/OPT connections on the PCB or replace the sensor
Check the CN7I/OAT connections on the PCB or replace the sensor
Check the CN9/OHT connections on the PCB or replace the sensor
Check the CN30/HP connections on the card or replace the sensor
Check the water flow
Check the water flow switch
Check the valve opening
Check the by-pass
Check the finned coil is not clogged
Water temperature too hot
Incondensable problem after maintenance, empty and evacuate the
cooling circuit
Refridgerant load too high, remove fluid into a liquid bottle
Check the AI/DI03 connections on the card or replace the sensor
Large gas leak, search for the leak with the detector
Air flow too low, check the ventilator rotation speed
Check the Finned Coil is not clogged, clean its surface
Check the AI/DI0 connections on the card or replace the sensor
Lack of water, check the filtration pump operation
Check the stop valve opening
Check the by-pass adjustment
Lack of water, check the filtration pump operation
Check the stop valve opening
Check the by-pass adjustment
Stop the heat pump, empty the condenser risk of freezing
Check the connections (see electrical diagram)
Stop heat pump operation, empty the condenser to avoid freezing,
by default the heat pump starts the filtration pump to avoid icing
over
Stop heat pump operation, empty the condenser to avoid freezing,
by default the heat pump starts the filtration pump and the heat
pump to avoid icing over.
Check free rotation; check CN97/DC connectors; replace the motor
Check the DCFAN/CN97 connector; replace the motor
Stop the heat pump