1. GENERAL INSTRUCTIONS - SAFETY Thank you for purchasing the Hayward heat pump for swimming pools. The Hayward FULL INVERTER heat pump has been designed to strict manufacturing standards meeting the highest levels of quality required. Hayward heat pumps offer you exceptional performance throughout your bathing season by adapting wattage, power usage and noise levels to the heating requirements of your swimming pool thanks to FULL INVERTER control logic.
Page 4
1. GENERAL INSTRUCTIONS - SAFETY (continued) This product contains refrigerant gas R32 This device contains R32. Never use a refrigerant other than R32. Any other gaseous body mixed with R32 could cause abnormally high pressure and lead to a failure or pipes bursting and injuring people.
Page 5
1. GENERAL INSTRUCTIONS - SAFETY (continued) Installation conditions • This heat pump is designed exclusively to heat swimming pool water; do not use this equipment for any other purpose. • Do not attempt to install this device by yourself. • If you detect a fault or any abnormal situation, do not install the heat pump and contact your dealer immediately.
Page 6
1. GENERAL INSTRUCTIONS - SAFETY (continued) • Verify that the drains flow well. • Verify the tightening of the hydraulic and electrical connections • Verify the hydraulic sealing of the condenser. • Have the leak-tightness of the cooling circuit to the leak detector checked by an accredited professional.
2. TECHNICAL SPECIFICATIONS 2.1 Heat pump technical data EASYTEMP Models ECPI15MA ECPI20MA ECPI30MA ECPI40MA FULL INVERTER Supply voltage 220V-240V /1ph/50Hz Refrigerant Load 0.350 0.430 0.480 0.650 Mass in teqCO 0.24 0.29 0.32 0.44 Leak check frequency No specific frequency, but an annual check is recommended Min--Max heating capacity 1.62--7.33 2.18--8.97...
The maximum heating temperature is set at 32°C to prevent damage to the liners. Hayward cannot be held responsible if used at a temperature above +32°C.
3. INSTALLATION AND CONNECTION 3.1 Functional Diagram Water Inlet Filter valve By-pass Pump valve filtration Water outlet Water outlet Chlorinator cell valve (or other treatment) Pool Note : The swimming pool heat pump unit is sold without any treatment or filtration equipment.
Page 11
3. INSTALLATION AND CONNECTION (continued) Do not position the device directly on the floor because this could cause problems. Favour positioning on the ground on anti-vibration studs. A wall bracket must not be used in conditions that can transmit vibrations. Do not install the heat pump on a support that risks intensifying the unit's vibrations.
3. INSTALLATION AND CONNECTION (continued) 3.3 Hydraulic connection The unit is supplied with two 50 mm Ø union connections. Connect the water inlet to the heat pump coming from the filtration group then connect the water outlet to the heat pump at the water conduit going to the pool (see diagram below).
3. INSTALLATION AND CONNECTION (continued) 3.4 Electrical connection Electrical installation and wiring for this equipment must be in conformity with local installation standards. NF C15-100 BS7671:1992 DIN VDE 0100-702 EVHS-HD 384-7-702 ÖVE 8001-4-702 MSZ 2364-702/1994/MSZ 10-553 1/1990 UNE 20460-7-702 1993, MSA HD 384-7-702.S2 RECBT ITC-BT-31 2002 Wiring Rules + IS HD 384-7-702...
3. INSTALLATION AND CONNECTION (continued) Never use an electrical plug for the power supply. The electrical power supply must have, in a suitable manner, an omnipolar protection device of the D-curve circuit breaker type as well as a 30mA protection differential circuit breaker (see following table). Models ECPI15MA ECPI20MA...
Page 15
3. INSTALLATION AND CONNECTION (continued) 8) Set the water flow using the by-pass valve (see § 3.6 and 2.1), as provided for by each model, to obtain an Entry/Exit temperature of 2°C. 9) After running for several minutes, verify that the air exiting the unit is cool (between 5 and 10°).
3. INSTALLATION AND CONNECTION (continued) 3.6 Water flow setting With the water entry and exit valves being open, adjust the by-pass valve in order to obtain a difference of 2°C between the inflow and outflow temperature (see principle diagram § 3.1). You can verify the switch by seeing the entry/ exit temperatures directly on the control panel.
4. USER INTERFACE 4.1 General presentation The heat pump is equipped with a digital control panel with a touch screen, electronically connected and pre-set at the factory in heating mode. Legend Water Input temperature Operating mode selection Defrost mode Adjust setpoint Operating mode Setting silence mode timer Activate silent mode...
Page 18
4. USER INTERFACE (continued) OFF mode ON mode When the heat pump is idle (in When the heat pump is running standby mode), OFF is displayed as or priming (setpoint reached), the shown on the screen. screen turns blue. The black screen indicates that the heat pump is idle;...
4. USER INTERFACE (continued) 4.2 Timer function settings The date and time can be set either in ON or in OFF mode. • Press 1 times on to return to the main screen.
4. USER INTERFACE (continued) 4.3 Setting the On/Off timers Setting this function is necessary if you would like to run the heat pump for a shorter period than what is defined by the filtration clock. Therefore, you can program a deferred start and an anticipated stop or simply stop a certain timeframe from running (at night, for example).
Page 21
4. USER INTERFACE (continued) Blue highlighting = Activated Grey = Deactivated • Press 2 times on to return to the main screen.
4. USER INTERFACE (continued) 4.4 Adjust setpoint The setpoint can be changed either in ON or in OFF mode with an accuracy of 0.5°C. • Press 1 times on to return to the main screen. It is recommended to never exceed 30°C to avoid alteration of the liners.
4. USER INTERFACE (continued) 4.5 Locking and unlocking the touch screen The screen can be locked or unlocked either in ON or in OFF mode. Lock activated Lock deactivated...
4. USER INTERFACE (continued) 4.6 SILENT function settings Silence mode enables the heat pump to be used in economic and very silent mode when the heating needs are low (maintaining the pool temperature or need for ultra-silent operation). This function can be Activated/Deactivated manually or using a Timer. Activation/Deactivation Silent mode deactivated Silent mode activated...
Page 25
4. USER INTERFACE (continued) Adjusting the SILENT mode Timer...
Page 26
4. INTERFACE UTILISATEUR (suite) • Press 2 times on to return to the main screen. The setting step is "hour to hour". Once the Timer is activated, it is active 7 days a week.
5. MAINTENANCE AND WINTERISING 5.1 Maintenance These maintenance operations must be carried out once per year in order to guarantee the longevity and the good working condition of the heat pump. • The maintenance and repairs of the device must be carried out by an accredited professional in accordance with the regulatory texts and the rules of the art in effect in the country where the device is installed (see §...
6. APPENDIX (continued) 6.2 Heating priority wiring for monophasic pump Dry contact 16 A max Power supply 230V / 50Hz Monophasic pump Terminals 1 and 2 deliver a potential-free dry contact, 230V / 50 Hz, no polarity. Wire terminals 1 and 2 as indicated in the diagram above, to activate the operation of the filtration pump in 2-minute cycles each hour if the temperature of the pool is lower than the set point.
6. APPENDIX (continued) 6.4 Troubleshooting guide Certain operations must be carried out by an authorized technician. If a fault occurs on the heat pump appears in the top left-hand corner of the screen. Refer to following table. Description Date and time Error codes of appearance When the problem is resolved, the error is automatically acknowledged...
Page 37
6. APPENDIX (continued) Error Problem Description Solution codes Verify the CN21/RES1 connectors on Water inlet sensor fault the board and the extension connector or replace the sensor Verify the N22/RES2 connectors on the Water outlet sensor fault board and the extension connector or replace the sensor Verify the CN12/PH connectors on the Outside temperature sensor fault...
Page 38
6. APPENDIX (continued) Error Problem Description Solution codes Lack of water, check the filtration pump operation Input/Output temperature difference Applicable in Cold mode only Check the stop valve opening > 13°C Check the by-pass adjustment Stop the heat pump, empty the Antifreeze protection Cold mode Water output temperature <...
No other costs (transportation, labour, etc.) are covered by the warranty. HAYWARD cannot be held liable for any direct or indirect damage caused by the incorrect installation, connection or operation of a product. Please contact your retailer if you want to make a claim under the terms of the warranty and request the repair or replacement of an item.