6.9. Single UPS operation

6.9.1. Operation of changing battery numbers through LCD menu
By default, the Balder 6000 UPS is set to operate with 2U battery cabinet
that contains 16 batteries of type 12V7Ah or 12V9AH (12V x 16 = 192V).
By default, Balder 10000 UPS is set to operate with 3U battery cabinet that
contains 20 batteries (12V x 20 = 240V).
However, for each of these models it is possible to set a different number
of batteries present in the attached cabinets (16 to 20 batteries, only for 3U
battery cabinet). To do this, you need to access a hidden settings menu, which
requires a password. Described below is how to set the number of batteries.
WARNING!
If you need to change the battery number this should be done before you connect
the battery cabinet to the UPS. After you set the battery number and completely
turn off the UPS, you can connect the battery cabinet to the UPS.
Description
LCD display
Step 1
UPS should be in bypass
mode. Then press the ESC
and UP keys for about 1
second at the same time.
You will enter the FW
version interface.
Step 2
You need to press the ESC
and UP keys for about 1
second at the same time
TWICE. You will enter the
interface where you need
to enter the password to
unlock hidden settings.
32
Step 3
Enter 103 password using
UP and DOWN keys; after
each digit press ENTER so
you can go to the next digit.
If the password is correct,
the interface appears as
follows.
Step 4
Press ESC and UP at
the same time to exit
the password interface.
Standard UPS display will
apprear.
NOTE!
Now you unlocked the hidden
parameter number 18 which
allows you to change the
number of batteries. To access
this parameter you need to
enter the settings menu of the
UPS.
Step 5
Press UP and DOWN
keys to enter the setting
interface. Go to parameter
18 using UP and DOWN
keys.
As shown in the figure, 20 is
the number of batteries.
33