7. Electrical connection

7. 7. 7. Heating connections
7. General description
General description
General description

7.1. Power supply

The electrical connection must be made by a qualifi ed
person and must be registered with the local electric-
ity company. The executive electrical company, is
responsible for the norm-compliant connection to the
electrical installation and the applied safety measure.
The mains voltage at the terminals of the heat pump
must be 230V respectively 400V ± 10%. The dimen-
sions of the connecting cables must be checked by
the executive electric company.
A fault-current circuit breaker for the heat pump
is not required. The connection to the protective
measure „protective multiple earthing" is suffi cient.
If nevertheless the protective measure „fault-current
circuit breakers," dispatched by the executive electric
company, a separate fault-current circuit breaker for
the heat pump is recommended.
56
Primary current electric immersion heater
AERO ILM 4-13
Installation instruction AERO ILM
This must be designed as an all current sensitive
Type B time-delayed (IΔN ≥ 300mA).
The specifi ed FI-types related to the heat pump ex-
cluding externally connected components (see Instal-
lation instructions, data sheets).
For the main current circuit as a result of the occur-
ring starting currents, circuit breakers with a tripping
characteristic curve Type „C" or „K" must be used.
For the control circuit and the optional electric auxiliary
heater, circuit breakers with a tripping characteristic
Type „B" or „Z" are suffi cient.
The electrical connection- and supply cables must be
designed as copper cables.
For electrical details see the wiring diagram.
3x400V/50Hz - 5G1,5 mm²
AERO ILM 2-7
1x230V/50HZ - 3G6,0 mm² or
3x400V/50Hz - 5G1,5 mm²
Primary current compressor
AERO ILM 4-13
AERO ILM 2-7
Control current
1x230V/50Hz - 3G1,5 mm²
Network cable
(optional)
All electrical details can be
derived from the appropriate
circuit diagram.
3x400V/50Hz - 5G4,0 mm²
1x230V/50HZ - 3G2,5 mm²
(C) IDM Energiesysteme GmbH