5. General description
Installation
The following shall be taken into account:
•
Occurring obstructions and their eff ect
•
Object refl ections
•
Ground refl ections
•
Absorption caused by plants
•
Eff ect of wind and temperature layers
10m
5m
5.6. Decoupling of buildings
If vibrations of the heat pump are transmitted via
fl oors, ceilings, walls or other solids, this is referred to
as structure-borne noise. In order to minimize this in,
heat pumps should be decoupled from the structure
in so far as possible. The installation of heat pumps
on ceilings or fl oors in lightweight construction should
be principally avoided. In the case of fl oating fl oor
screed the fl oor screed and impact sound insulation
should be omitted around the heat pump (as shown
in the illustration).
1. concrete floor
2. impact sound insulation
3. floor screed
4. cut
5. Sound reduction mat
5
4
3
2
1
24
10m
5m
Installation instructions AERO ILM
To the heat pump are enclosed two sound insulation
mats. If the heat pump is at the fi nal installation site,
the mats must be placed under the heat pump. For
this purpose, the four feet can be adjusted in height.
adjustable
feet of the
heat pump
view from above