Electrical Connection; Power Supply - iDM TERRA AL 60 Max Technical Documentation Installation Instructions

Air-water-heat pumps for outdoor installation with navigator 2.0 controler
Table of Contents

Advertisement

6. 6. 6 Exterior installation
6. General description
General description
General description

6. Electrical connection

6.1. Power supply

The electrical connection must be made by a qualifi
ed person and must be registered with the local elec-
tricity company. The executive electrical company, is
responsible for the norm-compliant connection to the
electrical installation and the applied safety measure.
The mains voltage at the terminals of the heat pump
must be 400 V ± 10 %. The dimensions of the con-
necting cables must be checked by the executive
electric company.
A fault-current circuit breaker for the heat pump is not
required. The connection to the protective measure
„protective multiple earthing" is suffi cient. If never-
theless the protective measure „fault-current circuit
breakers," dispatched by the executive electric com-
pany, a separate fault-current circuit breaker for the
heat pump is recommended.
If a heating element is used as a bivalence, the main power supply of the heating element is not
laid over the indoor unit, but is prepared by the customer on site.
A network socket is already provided on the bottom surface of the cabinet. For plug and play
usage of myiDM (heat-pump control via internet). The network cable have to be plugged in there.
For data transmission, a shielded cable must be used. All electrical details can be derived from
the appropriate circuit diagram.
31
Primary current heat pump (3+N 400V/50HZ)
Control current (1x230V/50HZ)
P
Primary current compressor
y
Control current
Data cable
Installation instructions TERRA AL 60 Max
This must be designed as an all current sensitive
Type B (IΔN ≥ 30 mA).
The specifi ed FI-types related to the heat pump
excluding externally connected components (see
Installation instructions, data sheets).
For the main current circuit as a result of the occur-
ring starting currents, circuit breakers with a tripping
characteristic curve Type „C" or „K" must be used.
For the control circuit and the optional electric auxiliary
heater, circuit breakers with a tripping characteristic
Type „B" or „Z" are suffi cient.
The TERRA AL 60 Max is equipped with two starting
current limiter.
The electrical connection- and supply cables must be
designed as copper cables.
For electrical details see the wiring diagram.
p
5x16 mm²
3x1.5 mm²
2x2x0.5 mm²
Sensor and control lines, on-
Network cable, on-site