Wind Direction; Decoupling From The Building; Space Requirements - iDM TERRA AL 60 Max Technical Documentation Installation Instructions

Air-water-heat pumps for outdoor installation with navigator 2.0 controler
Table of Contents

Advertisement

4. General description
Placement and Installation

4.10. Wind direction

When installing in windy areas (eg on the roof), the orientation of the machine must be selected in such a way
that the expected wind direction is turned by 90 degrees to the suction/exhaust direction of the heatpump.
wind direction

4.11. Decoupling from the building

The heat pump must be decoupled from the building in order to avoid structure borne noise. For example
when installing on a fl at roof

4.12. Space requirements

In order to guarantee maintenguarantee maintenance and operation of the heat pump, following minimum
distance has to be observed (for operation and maintenance). By observing this distance an unobstructed
system maintenance and operation can be guaranteed.
view from above
min. 200 mm
The minimum distances must be respected, because of the case of maintainance and to
prevent air-short-circuits.
20
suction
suction
exhaust
3270 mm
Installation instructions TERRA AL 60 Max
wind direction
exhaust
min. 1000 mm
min. 800 mm
heating side and electri-
cal connections
condensation outlet
(C) IDM Energiesysteme GmbH