Connections

Overview of outputs and

applications.

See also electrical diagrams earlier
in the manual
DI1
Digital input signal.
The defined function is active when the input is short-circuited/
opened. The function is defined in o02.
DI2
Digital input signal.
The defined function is active when the input is short-circuited/
opened. The function is defined in o37.
Pressure transmitter or temperature sensor S1
Pe / AKS 32R (pressure measurement recommended)
Connect to terminal 30, 31 and 32.
The signal from one pressure transmitter can be received by up
to 10 controllers. But only if there are no significant pressure
decreases between the evaporators to be controlled.
S1 (correct location is important to ensure correct measurements)
Pt 1000 ohm sensor
Connect to terminal 31 and 32.
S2
Pt 1000 ohm sensor
S3, S4, S5, S6
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of
the same type.
S3, air sensor, placed in the warm air before the evaporator
S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the
configuration)
S5, defrost sensor, placed on the evaporator
S6, product sensor or defrost sensor B or air sensor B.
The configuration determines which.
32
Application
DO1
1
2
3
4
5
6
7
8
9
10
Manual RS8EN502 © Danfoss 02-2010
DO2
DO3
DO4
DO5
DO6 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6
suction
hotgas
Blinds
heat
2
1
EKA Display
If there is be external reading/operation of the controller, display
type EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication
module is inserted in the controller. The module can be a LON
RS485 or a MODBUS.
Terminal 51 = screen
Terminal 52 = A (A+)
Terminal 53 = B (B-)
(For LON RS485 and gateway type AKA 245 the gateway must be
version 6.20 or higher.)
RJ45
For data communication, but only if a TCP/IP module is inserted in
the controller. (OEM specific)
MODBUS
For data communication.
Terminal 56 = screen
Terminal 57 = A+
Terminal 58 = B-
(Alternatively the terminals can be connected to an external
display type EKA 163A or 164A, but then they cannot be used
for data communication. Any data communication must then be
carried out by one of the other methods.)
Supply voltage
230 V a.c.
Version where sensor
connections have plug
connections.
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
• • •
P0/S1 S2
S3
S4
AK-CC 550
S5
S6
S5
S6
S5
S6
S5
S6
S5
S6
S5
S6
S5
S6
S5
S6
S5
S5B
S5
S3B

Hide quick links:

Advertisement

loading

This manual is also suitable for:

084b8020084b8021