GEM 639 eSyStep Operating Instructions Manual page 51

Motorized diaphragm valve
Hide thumbs Also See for 639 eSyStep:
Table of Contents

Advertisement

12.4.25 Actuator position feedback
The settings for the OPEN and CLOSED position feedback can be stored with the Actuator position feedback parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x51
1
0
R/W
2
16
R/W
3
32
RO
4
48
RO
Description of parameter values
Index name
Actuator position feed-
back
12.4.26 Initialized positions
The analog values of the initialized valve positions can be read out with the Initialized positions parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x53
1
0
RO
2
16
RO
3
32
RO
Description of parameter values
Index name
Initialized positions
www.gemu-group.com
Length
Index name
10 bits Actuator position
feedback
10 bits
10 bits
10 bits
Parameter
Values
Open request
30 ... 970
(3.0 ... 97.0%)
Close request
30 ... 970
(3,0 ... 97,0%)
Open real
0 ... 4095
Close real
0 ... 4095
Length
Index name
12 bits
Initialized
positions
12 bits
12 bits
Parameter
Values
Open
0 ... 4092
Close
0 ... 4092
Stroke
0 ... 4092
Parameter
Type
Open request
uint:16
Close request
uint:16
Open real
uint:16
Close real
uint:16
Request valve position OPEN
Request valve position CLOSED
Real valve position OPEN
Real valve position CLOSED
Parameter
Type
Open
uint:16
Close
uint:16
Stroke
uint:16
Analog value valve position OPEN
Analog value valve position CLOSED
Analog value stroke (difference between OPEN and
CLOSED).
51 / 67
12 Specific data IO-Link (pin 6)
Default
Values
900
30 ... 970
(90,0%)
(3,0 ... 97,0%)
100
30 ... 970
(10.0%)
(3.0 ... 97.0%)
0 ... 4095
0 ... 4095
Description
Default
Values
0
0 ... 4092
4092
0 ... 4092
0
0 ... 4092
Description
GEMÜ 639 eSyStep
OPEN / CLOSE (Code AE)

Advertisement

Table of Contents
loading

Table of Contents