Emerson Fisher 4320 Instruction Manual page 7

Wireless position monitor help
Hide thumbs Also See for Fisher 4320:
Table of Contents

Advertisement

4320 Position Monitor
October 2012
Table 1. Specifications (continued)
Electromagnetic Compatibility
Meets EN 61326‐1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326‐1 standard. Performance is
shown in table 2 below.
Emissions—Class A & B. Performance is shown in
table 3 below.
ISM equipment rating: Group 1, Class A & B
Vibration Testing
Meets or exceeds vibration levels specified in
ANSI/ISA 75.13.01 1996 (2007):
4 mm peak to peak at 5 Hz,
2 GHz from 15­150 Hz, and
1 GHz from 150­ 2000 Hz
European Directive Information
This product complies with the following directives:
ATEX Directive (94/9/EC)
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Radio and Telecommunications Terminal Equipment
Directive (R&TTE) (1999/5/EC)
Refer to the Safety Instructions (D103022X012) for
the Declaration of Conformity
Operating Temperature Limits
Monitoring only:
-40 to 85_C (-40 to 185_F)
LCD may not be readable below -20_C (-4_F)
With Pneumatic Output (On/Off Control):
-20 to 50_C (-4 to 122_F)
Temperature Sensitivity
0.06% change per degree C
Storage Temperature Limits
-40 to 70_C (-40 to 158_F)
Humidity Limits
10-95% Non‐Condensing Relative Humidity
6
(2)(3)
(2)(3)
Electrical Classification
CSA (C/US)— Intrinsically Safe
ATEX— Intrinsically Safe
IECEx— Intrinsically Safe
Refer to Hazardous Area Classifications and Special
Instruction for "Safe Use" and Installations in
Hazardous locations, starting on page 13, for
additional information
Electrical Housing
4X & IP66
IEC 61010 Compliance
Meets Pollution Degree 2
Adjustments
Zero and Maximum Span through local interface
Weight
Monitoring— 0.57 kg (1.25 lbs)
On/Off Control— 1.6 kg (3.4 lbs)
Power Module
Standard —Lithium, non‐rechargeable
Power Module Limits
Standard— 5 years at update rate of 16 seconds or
longer with 3 additional devices communicating
through it
Extended‐Life— 10 years at update rate of 8 seconds
or longer with 3 additional devices communicating
through it.
Shelf life— 10 years (radio off)
‐continued‐
Instruction Manual
(3)
(4)
D103621X012

Advertisement

Table of Contents
loading

Table of Contents