Instruction Manual
October 2009
Power Module Limits
Standard —5 years @ 1 minute update rate with
3 additional devices communicating through it
Extended−Life —6 years @ 4 second rate with 3
additional devices communicating through it
Shelf life —15 years (radio off)
Update Rates
For position feedback, temperature, and power
1. The pressure/temperature limits in this manual and any applicable standard or code limitation for valve should not be exceeded.
2. Due to the combustible nature of the lithium content, the power module has special installation, operation, storage, and/or shipping requirements. Observe all warnings included with the
power module before installing, operating, storing, or shipping. Contact your Emerson Process Management sales office if additional information is needed.
3. Contact your Emerson Process Management sales office for information on pending third party approvals.
Table 2. EMC Summary Results—Immunity
PORT
PHENOMENON
Electrostatic discharge (ESD)
Radiated EM field
Enclosure
Rated power frequency
magnetic field
Performance criteria: +/− 2% of effect
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Table 3. EMC Summary Results—Emissions
FREQUENCY
PORT
RANGE (MHz)
30 to 230
230 to 1000
Enclosure
1000 to 3000
3000 to 6000
NOTES:
The 4310 is considered as a Group 1 device.
Industrial, Scientific, and Medial (ISM) radio frequency (RF) equipment is rated according to its Group and Class as follows;
Group I − Equipment in which there is intentionally generated and/or used conductively coupled radio−frequency energy which is necessary for the internal functioning of the equipment
itself.
Group II − Equipment in which radio−frequency energy is intentionally generated and/or used in the form of electromagnetic radiation for the treatment of material, and EDM and arc
welding equipment.
Class A − Equipment suitable for use in industrial and commercial environments
Class B − Equipment suitable for use in domestic environments
Table 1. Specifications (continued)
BASIC
STANDARD
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-8
BASIC
STANDARD
Group 1 Class A: 40 dB (uV/m) measured at 10 m distance
Group 1 Class B: 30 dB (uV/m) measured at 10 m distance
Group 1 Class A: 47 dB (uV/m) measured at 10 m distance
Group 1 Class B: 37 dB (uV/m) measured at 10 m distance
EN 55011
Group 1 Class B
50 dB (uV/m) measured at 3 m distance, peak limit not to exceed 70 dB (uV/m)
Group 1 Class B
54 dB (uV/m) measured at 3 m distance, peak limit not to exceed 74 db (uV/m)
4310 Wireless Position Monitor
module voltage—selectable from 4 seconds to 1
hour, 4s, 8s, 16s, 32s, 1 to 60 minutes
Factory default is 1 minute
Construction Material
Housing: Engineered resin
TEST LEVEL
6 kV contact
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 10V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 3V/m with 1 kHz AM at 80%
30 A/m at 50 Hz & 60 Hz
100 A/m @ 50 Hz
EMISSIONS LEVEL
PERFORMANCE
(1)
CRITERIA
B
A
A
GIVEN
RATING
Class A & B
Class A & B
Class A &B
Class A & B
3