Emerson TopWorx 4310 Instruction Manual page 17

Wireless position monitor
Hide thumbs Also See for TopWorx 4310:
Table of Contents

Advertisement

Instruction Manual
October 2009
Field Communicator
1 Offline
2 Online
3 Frequency Device
4 Utility
Online
1 Overview
2 Configure
3 Service Tools
D Power Module Voltage—indicates the status of
the power module voltage.
D Accumulated Cycles—indicates the number of
accumulated cycles.
D Time Since Reset—indicates the time (in hours,
minutes, and seconds) since the last time the 4310
was restarted.
Run Time Extremes
D Max Recorded Temp—indicates the maximum
recorded temperature of the 4310.
D Date of Max Temp—indicates when the
maximum temperature was recorded.
D Min Recorded Temp —indicates the minimum
recorded temperature of the 4310.
D Date of Min Temp—indicates when the
minimum temperature was recorded.
Service Tools
1 Show Active Alerts
3
2 Variables
3 Run Time Extremes
4 Maintenance
Figure 17. Field Communicator Menu Tree—Service Tools
4310 Wireless Position Monitor
Variables
1 Switch Status
3-2
2 Electronics Temp
3 Power Module Voltage
4 Accumulated Cycles
5 Time Since Reset
Run Time Extremes
3-3
1 Max Recorded Temp
2 Date of Max Temp
3 Min Recorded Temp
4 Date of Min Temp
3-4
Maintenance
1 Calibration
2 Reset Device
Maintenance
D Calibration
Calibration Status—indicates the status of the last
instrument calibration.
Calibration Date—indicates when the instrument
was last calibrated.
Calibrate—allows you run a calibration on the
instrument. Follow the prompts on the Field
Communicator to calibrate the instrument.
D Reset Device—performs a reset of the
instrument firmware.
Calibration
3-4-1
1 Calibration Status
2 Calibration Date
3 Calibrate