Settings; Initial Configuration - KMC Controls BAC-19 FlexStat Series Application Manual

Hide thumbs Also See for BAC-19 FlexStat Series:
Table of Contents

Advertisement

Settings (Press Space Temp)
Rotation Values
Fan Auto or (Constant) On
Occupancy Override
Time and Date

SETTINGS

NOTE: Select the (AHU, HPU, RTU, or FCU)
application and units BEFORE
changing any other settings. Changing
applications later will reset most
settings back to their defaults. Use
Restore APP in the Advanced menu
or software to verify or change
applications. See
Options) on page
NOTE: Available menu options depend on
the FlexStat model and selected
application. Some options may require
custom Control Basic for operation
(e.g., DCV functions using an external
CO
sensor).
2
NOTE: Some changes to settings will not
affect operation until after the FlexStat
is restarted.
BAC-19xxxx FlexStat Application Guide
Press to Change Settings
(Default Screen Configuration Shown)
Advanced (Menu
4.
NOTE: Software is required for fully configuring
alarms and trends, adding custom
Control Basic code, and customizing
the display—see
on page
see the
data
sheet.

Initial Configuration

For initial FlexStat configuration, following the
menu steps in this order is recommended.
1. Check that the desired (AHU, FCU, HPU, or
RTU) application is selected. If not, select it
and restart the FlexStat. See Restore APP in
Advanced (Menu Options) on page
NOTE: Changing the application later will
reset most settings back to their
defaults!
3
Active Cooling Setpoint
Active Heating Setpoint
Units (°F or C)
Heat/Cool/Auto/Off Mode
Motion Sensor (Not a Button)
Display Customization
9. For compatible software,
BAC-190000 Series FlexStats
4.
AG200824A