Start learns as days pass the optimal times to
begin and end occupied mode and adjusts the
schedule times accordingly.
• DCV Mode = Select None, Basic, or Standard
DCV mode. See
CO2 Sensors and DCV
Operation on page
• AUX Heat = Select None, 3rd stage, or
Compressor Lockout for (HPU) Auxiliary Heat.

Trends and Alarms

NOTE: Trend logs for the space temperature,
active cooling setpoint, and active
heating setpoint are created by default.
Use KMC software to access these
features.

PASSWORDS

FlexStats have security options for two levels of
passwords as described below and in
(Menu Options) on page
LEVEL
DEFAULT
PROTECTS DESCRIPTION
Level 1
0000
Level 2
(See the
Conquest
Controllers
Default
Configuration
Password
Technical
Bulletin)
NOTE: If an optional Level 1 password is
set, users must enter that password
to change a setpoint. No password
required (0000) is the default.
NOTE: FlexStats are factory-set with a default
Level 2 password for configuration.
For more information about the default
password, log in to the KMC web site
and see the
Default Password Technical
NOTE: For security purposes, change the
controller's default password(s). Be
sure to document any changes made
to passwords!
BAC-19xxxx FlexStat Application Guide
11.
Advanced
4.
Setpoints
Four digits, with
each digit being a
number 0 to 9. If
all four numbers
are 0, no pass-
word is required
of the user for
that level.
Conquest Controllers
Bulletin.

COMMUNICATION OPTIONS

Configuration via Display Menus

NOTE: FlexStat communications can be set
in the built-in display menu system or
through software.
Use the built-in menus to select the appropriate
MS/TP or Ethernet/IP communication method and
address information. See
Options) on page

Ethernet/IP Configuration via Software

"E" model FlexStats have a default configuration of
BACnet Ethernet and a Device ID of 1. To config-
ure the FlexStat to BACnet IP using KMC software
(see the
BAC-190000 Series FlexStats data sheet
for versions that support FlexStats), perform the
following steps:
1. If necessary to see the FlexStat under Network
Manager, add or change a port in BACstac to
Ethernet:
A. Click the Microsoft
at the lower left corner of the screen.
B. Click Cimetrics.
C. Click Configure BACstac.
Creating an Ethernet Port in BACstac
D. Click Add.
7
Communications (Menu
5.
Windows
Start Menu
®
®
Starting BACstac
AG200824A