KMC Controls KMCConquest FlexStat BAC-19 Series Sequence Of Operation

Hide thumbs Also See for KMCConquest FlexStat BAC-19 Series:

Advertisement

Quick Links

CONTENTS
Introduction .........................................................1
Applications by Model ...........................................1
General Wiring Considerations ................................2
DCV (Demand Control Ventilation) ...........................3
Air Handling Unit (BAC-19xx36) ..............................4
Inputs and Outputs List .....................................4
Wiring ............................................................5
Sequence of Operation ......................................6
Inputs and Outputs List .....................................7
2-Pipe Wiring...................................................8
2-Pipe Sequence of Operation ............................9
4-Pipe Wiring................................................. 10
4-Pipe Sequence of Operation .......................... 11
Inputs and Outputs List ................................... 12
Wiring .......................................................... 13
Sequence of Operation .................................... 14
Heat Pump Unit (BAC-19xx63) .............................. 15
Inputs and Outputs List ................................... 15
Wiring .......................................................... 16
Sequence of Operation .................................... 17
Roof Top Unit (BAC-19xx63) ................................. 18
Inputs and Outputs List ................................... 18
Wiring .......................................................... 19
Sequence of Operation .................................... 20
Important Notices ............................................... 21
Support ............................................................. 21
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553
NOTICE
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
BAC-19xxxx FlexStat
Sequence of Operation and Wiring Guide

INTRODUCTION

This guide describes sequences of operation and
wiring for different applications of KMC Conquest
BAC-19xxxx FlexStats.
For general installation and configuration proce-
dures, see the
Guide
at kmccontrols.com.
For configuration of settings, passwords, com-
munication options, display customization, wiring
considerations, and troubleshooting, see the
19xxxx FlexStat Application
For specifications and accessories, see the
190000 Series FlexStat Data
For instructions on custom configuration and
programming, see the Help system in the software
tool.

APPLICATIONS BY MODEL

BAC-19xx36C models:
• Air Handling Units
• Unit Ventilators (4-Pipe)
BAC-19xx63C models:
• Fan Coil Units (2- and 4-Pipe)
• Heat Pump Units
• Roof Top Units
/
877.444.5622
/
Fax: 574.831.5252
KMCConquest
Automation Hardware
BAC-19xxxx FlexStat Installation
Guide.
Sheet.
/
www.kmccontrols.com
TM
BAC-
BAC-

Advertisement

Table of Contents
loading

Summary of Contents for KMC Controls KMCConquest FlexStat BAC-19 Series

  • Page 1: Table Of Contents

    OBSERVE PRECAUTIONS • Unit Ventilators (4-Pipe) FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES BAC-19xx63C models: • Fan Coil Units (2- and 4-Pipe) • Heat Pump Units • Roof Top Units KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 877.444.5622 Fax: 574.831.5252 www.kmccontrols.com...
  • Page 2: General Wiring Considerations

    GENERAL WIRING CONSIDERATIONS • Because of the many connections (power, network, inputs, outputs, and their respective NOTE: See the BAC-19xxxx FlexStat grounds or switched commons), be sure Application Guide for more important wiring is well planned before installation of information about network and other conduit! wiring.
  • Page 3: Dcv (Demand Control Ventilation)

    DCV (DEMAND CONTROL VENTILATION) See the BAC-19xxxx FlexStat Application Guide for more information. See also: BAC-195xxx and BAC-193xxx model FlexStats in- clude CO sensors for DCV operation in (6/3) RTU, • Air Handling Unit (BAC-19xx36) on page 4 HPU, 4-pipe FCU, and (3/6) AHU applications with •...
  • Page 4: Air Handling Unit (Bac-19Xx36)

    AIR HANDLING UNIT (BAC-19XX36) Inputs and Outputs List NOTE: See also DCV (Demand Control Ventilation) on page Inputs (AI1) INTERNAL Space Temperature Sensor* NOTE: Binary Output (BO1—BO3) terminals AI2/IN2 Remote Room Temp. Sensor are relays and are used with SC AI3/IN3 Discharge Air Temperature AI4/IN4...
  • Page 5: Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 6: Sequence Of Operation

    CLG SPAN ROOM TEMP HTG SPAN CLG SPAN ROOM TEMP INCREASE INCREASE © 2020 KMC CONTROLS, INC. BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide AG200123C 19476 INDUSTRIAL DR. DRAWING TITLE: NEW PARIS, IN 46553 CREATION DATE: 1/2/2020 FILENAME: KA19001-2 PHONE: 574.831.5250...
  • Page 7: (2-Pipe And 4-Pipe) Fan Coil Unit (Bac-19Xx63)

    (2-PIPE AND 4-PIPE) FAN COIL UNIT (BAC-19XX63) Inputs and Outputs List FCU (2-PIPE) FCU (4-PIPE) Inputs Inputs (AI1) INTERNAL Space Temperature Sensor* (AI1) INTERNAL Space Temperature Sensor* AI2/IN2 Remote Room Temp. Sensor AI2/IN2 Remote Room Temp. Sensor AI3/IN3 Discharge Air Temperature AI3/IN3 Discharge Air Temperature AI4/IN4...
  • Page 8: 2-Pipe Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 9: 2-Pipe Sequence Of Operation

    CLG SPAN ROOM HTG SPAN CLG SPAN ROOM TEMP TEMP INCREASE INCREASE © 2020 KMC CONTROLS, INC. 19476 INDUSTRIAL DR. BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide DRAWING TITLE: AG200123C NEW PARIS, IN 46553 CREATION DATE: 1/2/2020 FILENAME: KF1940A-2 PHONE: 574.831.5250...
  • Page 10: 4-Pipe Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 11: 4-Pipe Sequence Of Operation

    HTG SPAN CLG SPAN HTG SPAN CLG SPAN TEMP TEMP INCREASE INCREASE © 2020 KMC CONTROLS, INC. 19476 INDUSTRIAL DR. DRAWING TITLE: BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide AG200123C NEW PARIS, IN 46553 CREATION DATE: 1/2/2020 FILENAME: KF1940A-2 PHONE: 574.831.5250...
  • Page 12: (4-Pipe) Unit Ventilator (Bac-19Xx36)

    (4-PIPE) UNIT VENTILATOR (BAC-19XX36) Inputs and Outputs List NOTE: For Fan Coil Unit applications (no (4-PIPE) UNIT VENTILATOR outside air damper), see (2-Pipe and Inputs 4-Pipe) Fan Coil Unit (BAC-19xx63) (AI1) INTERNAL Space Temperature Sensor* on page AI2/IN2 Remote Room Temp. Sensor AI3/IN3 Discharge Air Temperature NOTE: See also...
  • Page 13: Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 14: Sequence Of Operation

    CLG VLV AUTO AUTO HTG SPAN CLG SPAN ROOM HTG SPAN CLG SPAN ROOM TEMP TEMP INCREASE INCREASE © 2020 KMC CONTROLS, INC. BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide AG200123C 19476 INDUSTRIAL DR. DRAWING TITLE: NEW PARIS, IN 46553...
  • Page 15: Heat Pump Unit (Bac-19Xx63)

    HEAT PUMP UNIT (BAC-19XX63) Inputs and Outputs List NOTE: Binary Output (BO1—BO6) terminals are relays and are used with SC Inputs terminals instead of GND terminals. (AI1) INTERNAL Space Temperature Sensor* AI2/IN2 Remote Room Temp. Sensor NOTE: Universal (analog) inputs (AIx/INx) and AI3/IN3 Discharge Air Temperature outputs (AOx/OUTx) are used with GND...
  • Page 16: Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 17: Sequence Of Operation

    ROOM TEMP INCREASE 2.0F 1.0F HTG SPAN CLG SPAN ROOM TEMP INCREASE © 2020 KMC CONTROLS, INC. 19476 INDUSTRIAL DR. DRAWING TITLE: BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide AG200123C NEW PARIS, IN 46553 FILENAME: KH19001-2 PHONE: 574.831.5250 CREATION DATE: 1/2/2020 FAX: 574.831.5252...
  • Page 18: Roof Top Unit (Bac-19Xx63)

    ROOF TOP UNIT (BAC-19XX63) Inputs and Outputs List NOTE: See also DCV (Demand Control Ventilation) on page Inputs (AI1) INTERNAL Space Temperature Sensor* NOTE: Binary Output (BO1—BO6) terminals AI2/IN2 Remote Room Temp. Sensor are relays and are used with SC AI3/IN3 Discharge Air Temperature AI4/IN4...
  • Page 19: Wiring

    If controllers are to be networked together via MS/TP, turn ON EOL switch on the controllers at both physical ends Line of the network. Connect shield wires Voltage together and to earth ground at only one point, but do not connect to controllers. From previous controller...
  • Page 20: Sequence Of Operation

    ROOM TEMP INCREASE 1.0F 2.0F HTG SPAN CLG SPAN ROOM TEMP INCREASE © 2020 KMC CONTROLS, INC. 19476 INDUSTRIAL DR. DRAWING TITLE: BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide AG200123C NEW PARIS, IN 46553 FILENAME: KR19001-2 PHONE: 574.831.5250 CREATION DATE: 1/2/2020 FAX: 574.831.5252...
  • Page 21: Important Notices