EXTERNAL BATTERY CABINETS (XBAT) – CONNECTION PROCEDURE
External batteries must be connected to UPS by using original XMART DC cable provided inside the box.
IMPORTANT: All OPTIMA-T10 6K and 10K work with 240VDC battery voltage. This voltage is provided by battery packs
by connecting 20 batteries 12VDC in series. There could be some UPS models working with a different DC voltage. User
must check carefully XBAT voltage is compatible with the UPS DC voltage before making DC connections.
In case electrical information given by this manual does match with information provided by product labels, user must
consider information on labels or printed on the product.
1)
Place UPS module close to original XMART XBAT modules.
2)
Check all DC breakers in XBAT are in OFF position.
3)
Connect UPS to first XBAT module by using original DC cable
4)
In case system has more than 1 XBAT, connect XBAT#1 to XBAT#2, then XBAT# 2 to XBAT#3 and so on.
DC CABLES
Original XMART DC cables are 1 meter long. They come with safety connectors (UL) easy to plug into the UPS and into battery cabinets.
These cables can be connected and disconnected without powering the UPS off.
www.xmart-ups.com
USER MANUAL – OPTIMA-T10 6K/10K (UL)
VER.190731-GA2UL (ENG)