11� Technical specifications
Dimensions W × H × D
Supply voltage
Sensor system
Reach
Angle of coverage
Output
Output, switching
output 2presence
(COM 2 only)
Light-level setting
Switching output 1
Switching output 2
only COM2 for HVAC
Mounting height
Time setting
IP rating
Temperature range
*
At extreme angles, the reach of the
conditions.
80 × 80 × 50 mm
220-240 ~V / 50/60 HZ
Passive infrared (IR) / high-frequency (HF)
IR max. 12 m (tangential) /
max. 4 m (radial) / HF max. 8 m
180°
Incandescent / halogen lamp load
Fluorescent lamps, electronic ballast
Fluorescent lamps, uncorrected
Fluorescent lamps, series-corrected
Fluorescent lamps, parallel-corrected
Low-voltage halogen lamps
LED < 2 W
2 W < LED < 8 W
LED > 8 W
Capacitive load
max. 230 W / 230 V
max. 1 A (cos φ = 1)
for HVAC (heating/ventilation / air-conditioning)
10-1000 lux, ∞ / daylight
30 s - 30 min, pulse mode (approx. 2 s),
Time setting, IQ mode time (automatic adjustment to
usage profile)
Time setting 0 or 10 min switch-ON delay.
5-15 min stay-ON time via (RC)
1 min - 2 h stay-ON time via Smart Remote
Automatic room surveillance
1.1 m
30 s - 30 min
IP20
0°C to 40°C
HF 180 is extensively determined by local
- 32 -
*
2000 W
1000 W
1000 VA
400 VA
500 VA
2000 VA
100 W
300 W
600 W
176 μF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ir 180Ir 180 com1Ir 180 com2Hf 180 com1

Table of Contents