Code for basic mode: updwd123
Code for professional mode: adm123
Note: You will find an application
description at knx.steinel.de.
1. Issue physical address and generate
application program in the ETS.
2. Load the physical address and appli-
cation program into the human pres-
ence detector. If you are prompted to
do so, activate the programming mode
under settings.
Note: The HPD2 has a learning-in time of
approx. 30 minutes. Do not enter the
room during this period as the HPD2 is
learning the room's characteristics.
Windows or other panes of glass should
be identified as non-detection zones as
miscounts may otherwise occur.
Further information is available under
"Help" in the HPD2 web interface.
Function Reset Button
• Press and hold < 5s
(blinking period 400ms): turn off KNX
programing mode
• Press and hold 5s - 10s
(blinking period 200ms): turn on KNX
programing mode
• Press and hold 10s - 15s
(blinking period 120ms): restart
• Press and hold > 15s (blinking stops):
reset to factory defaults

7. Troubleshooting

Persons identified
– Persons within the detection zone
or the defined detection footprint
• Check detection zone
• Reduce sensor sensitivity
(web browser)
Persons not being identified
– Persons cannot be identified by the
sensor
– Persons only partially identifiable
(leg, shoulder, head)
• Ensure unobstructed sensor vision
• Make sure that persons are not
concealed by plants etc.
• Increase sensor sensitivity (web browser)
8. Maintenance / care
• No maintenance possible.
• The detector lens may be cleaned with
a damp cloth if it becomes dirty (do
not use cleaning agents).
9. Disposal
Electrical and electronic equipment, acces-
sories and packaging must be recycled in
an environmentally compatible manner.
Do not dispose of electrical and
electronic equipment as
domestic waste.
EU countries only:
Under the current European Directive on
Waste Electrical and Electronic Equip-
ment and its implementation in national
law, electrical and electronic equipment
no longer suitable for use must be
collected separately and recycled in an
environmentally compatible manner.

10. Manufacturer's warranty

As purchaser, you are entitled to your
statutory rights against the vendor. If these
rights exist in your country, they are neither
curtailed nor restricted by our Warranty
Declaration. We guarantee that your
- 14 -
STEINEL Professional sensor product will
remain in perfect condition and proper
working order for a period of 5 years. We
guarantee that this product is free from
material-, manufacturing- and design flaws.
In addition, we guarantee that all electronic
components and cables function in the
proper manner and that all materials used
and their surfaces are without defects.
Making Claims
If you wish to make a claim, please send
G B
your product complete and carriage paid
with the original receipt of purchase, which
1
3
Y E A R
Y E A R
must show the date of purchase and prod-
uct designation, either to your retailer or
MANUFACTURER'S
MANUFACTURER'S
WARRANTY
WARRANTY
contact us at STEINEL (UK) Limited,
25 Manasty Road, Axis Park, Orton
Southgate, Peterborough, PE2 6UP,
for a returns number. For this reason, we
recommend that you keep your receipt of
purchase in a safe place until the warranty
period expires. STEINEL shall assume no

11. Technical specifications

Dimensions (H × W × D)
Power supply
Sensor type
Application
Mounting
Mounting height
Angle of coverage
Detection limitation
Reach
Temperature range
IP rating
Light value
Value range for temperature sensor
Value range for humidity sensor
liability for the costs or risks involved in
returning a product.
For information on making claims under
the terms of the warranty, please go to
www.steinel-professional.de/garantie
If you have a warranty claim or would like to
ask any question regarding your product,
you are welcome to call us at any time on
our Service Hotline 01733 366700.
5
Y E A R
MANUFACTURER'S
WARRANTY
156 × 86 × 52 mm
KNX bus 21 - 30 V DC, 10 mA
Additional voltage 21-32 V DC, 200 mA
Camera
Indoors
Vertical wall
2.3 - max. 6 m
110°
Max. 5 detection zones /
Max. 3 non-detection zones
10 m
0°C to 40°C
IP20
2 - 2000 lux
0°C - 40°C +/- 1°C
20% - 90% +/- 5%