Delta PCS100 Installation Manual page 65

Power conditioning system
Hide thumbs Also See for PCS100:
Table of Contents

Advertisement

Table 17: Technical Specifications of Delta PCS100 (Continued)
Item
Crest Factor
Environment
Max Altitude
Operating Temperature
Storage Temperature
Humidity
Cooling
Pollution Degree
Acoustic Noise
IP Degree
Interface & Communication
Digital I/O
User Interface
Emergency Stop
Communication
System Characteristic
Peak Efficiency
Standby Loss
Dimensions (W x D x H) (excl.
Package)
Net Weight (excl. Package)
Standard Compliance
Certificate
Product Conformity
Applicable Battery Chemistry
Table 18: Icc declaration (r.m.s. value, Icp,mr, device)
Ports
Icc
Icp,mr
AC
25kA
5kA
DC
20kA
5kA
Installation Manual
2.0 @ rated power
3,000 m
≤ 2000 m: -25 ~ 60º C, derating > 50º C (3%/º C),
-25 ~ 40º C, > 2000 m
-25 ~ 70º C
0 to 95% RH, no-condensing
Fan cooled, speed controlled and alarmed signal
3
< 72 dB, @ 1m
IP55
3 x Input, 0 - 24 V
2 x Output relays
4.9 inch LCD screen with operation button, Fault LEDs
Local EPO button & remote control
RS-485 / Modbus RTU, Ethernet/ Modbus TCP
97.9%
< 25 W @Sleep Mode
600 mm x 800 mm x 1,766 mm / 23.6 in x 31.5 in x 69.5 in
310 kg / 683 lbs
IEC/EN 62477-1,
VDE-AR-N4105, G99, AS/NZS 4777.2
IEC/EN 61000-6-2, IEC/EN 61000-6-4 (Class A)
CE, RCM
Lithium-ion, flow battery
Type
Location
FU1, FU2,
170M1371,
Bussmann
FU3
170M1813,
FU4,FU5
Bussmann
61
Description
Characteristics of SCPD
Specification
Rated current: 250A; rated voltage:690V;
Interrupt rating: 200kA RMS Sym.
Rated current: 250A; rated voltage:1000V;
breaking capacity: 50kA.
Appendix

Hide quick links:

Advertisement

Table of Contents
loading