Installation
Maintenance distance requirements
A minimum distance of 800 mm behind the PCS is required for maintenance from rear side, a
minimum distance of 800mm in front of the PCS is required for maintenance from front side and a
minimum distance of 100mm on top of the PCS is required for lifting the PCS if needed as shown in
Figure 7.
Figure 7. Front and Rear Maintenance Clearance Distance
Opening the door space
When installing the PCS, take into consideration the necessary ventilation space as well as the space
requirements to allow access when opening the doors. At the same time, 306mm opening the door
space should be reserved as shown in Figure 8.
Figure 8. Top View of Door Clearance
Parallel installation
When PCS are installed side by side, the clearance between PCS should be greater than 10 mm as
shown in Figure 9.
Figure 9. Top View of Side by Side
Installation Manual