4.3

Selecting an Input

The Benchtop Meter features a User Programmable Universal Input. Select the input
type using TABLE 10. Initialization Mode Menu, below. Refer to Section 3.1.2 to 3.1.3
for Input Wiring Diagrams.
Level
Level
Level
1
2
3
INIT
INPt
t.C.
Rtd
tHRM
PRoC
Level
Level
Level
4
5
6
k
J
t
E
N
R
S
b
C
N.wIR
3 wI
4 wI
2 wI
A.CRV 385.1
385.5
385.t
392
3916
2.25k
5k
10k
4–20
Note:
This Manual and Live Scaling submenu is the same for all PRoC ranges.
MANL
Rd.1
IN.1
Rd.2
IN.2
LIVE
Rd.1
IN.1
Rd.2
IN.2
0–24
+-10
+-1
+-0.1
Table 10. Selecting Inputs.
13
Level
7
Type K thermocouple
Type J thermocouple
Type T thermocouple
Type E thermocouple
Type N thermocouple
Type R thermocouple
Type S thermocouple
Type B thermocouple
Type C thermocouple
3-wire RTD
4-wire RTD
2-wire RTD
385 calibration curve, 100 Ω
385 calibration curve, 500 Ω
385 calibration curve, 1000 Ω
392 calibration curve, 100 Ω
391.6 calibration curve, 100 Ω
2250 Ω thermistor
5000 Ω thermistor
10,000 Ω thermistor
Process input range: 4 to 20 mA
-----
Low display reading
-----
Manual input for Rd.1
------ High display reading
-----
Manual input for Rd.2
-----
Low display reading
-----
Live Rd.1 input, ENTER for current
-----
High display reading
-----
Live Rd.2 input, ENTER for current
Process input range: 0 to 24 mA
Process input range: -10 to +10 mA
Process input range: -1 to +1 mA
Process input range: -0.1 to +0.1 mA
Notes