10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Maximum dynamic
gradient frequency
50.22 – 70.5 [Hz]
Minimum dynamic
gradient frequency
45 – 50 [Hz]
P(f) settling time
200 – 2,000 [ms]
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% / min]
10.3

FRT

Dynamic grid support (Fault Ride Through)
A generation plant's ability to remain immune to voltage drops and voltage spikes in the supply system is a key
element in establishing a reliable energy supply. Immunity to interference ensures that brief disruptions do not
result in a loss of generation capacity in a larger range of an interconnected grid. Grid support by a fast feeding
of residual current also limits the spatial extent of the incident.
With its dynamic grid support by way of immunity, the device has this characteristic. The ability to remain on
the grid is particularly relevant. The protective settings also determine the device's ability to remain on the grid
or not. Protective settings take the upper hand over the capacity of immunity to interference.
10.3.1 Dynamic grid support by way of immunity to interference
Interference immunity against undervoltage
Voltage drop above the limit curve in can be overcome without the need for shutdown from the grid. The feed-
in power remains constantly within the limits of the maximum continuous current of the inverter.
If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage
returning.
Page 64
Dynamic gradient maximum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum char-
ging power if the frequency rises to the maximum configured frequency.
Dynamic gradient minimum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum feed-in
power if the frequency drops to the minimum configured frequency.
Determines the dynamic behaviour in the event of a change in the act-
ive power limit. In the event of a change in frequency, the active power
is altered subject to a PT-1 characteristic curve using a settling time of 5
Tau.
The settling time is overlaid with the increasing and decreasing gradient.
Specifies the dynamic response on changing the active power for power
increase and decrease. With a voltage change, the active power is
changed with the specified gradient.
Note: The gradient is overlaid with the settling time.
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Manual