10 | Specifications
Country-
Me-
Display/
spec. Set-
nu
Setting
tings
level
Tiempo de desact.
0 – 3,600 [s] /
[s] /
1[s]
Grad. de desact.
1 – 60,000 [% /
min] /
1
Maximum dynamic gra-
dient frequency
50,22 – 70,5 [Hz]
0.01 [Hz]
Minimum dynamic gra-
dient frequency
45 – 50 [Hz]
[Hz]
Gradiente salida ascen-
1
2
3
4
4
diente & Gradiente sa-
lida decreciente
1–65 534 [% / min]
10.3

FRT

Apoyo dinámico a la red (Fault Ride Through)
La resistencia a las interferencias de las instalaciones de autogeneración a las caídas y picos de tensión en el sis-
tema de suministro es de gran importancia para un suministro de energía fiable. La resistencia a las interferen-
cias garantiza que los incidentes de interferencia momentánea no den lugar a la eliminación de la capacidad de
autogeneración pertinente en una zona más amplia de la red interconectada. El apoyo de la red mediante la rá-
pida alimentación de corriente de defecto reduce, además, la extensión del evento en el espacio.
El equipo cumple la característica de resistencia dinámica a la red debido a la resistencia a las interferencias. La
capacidad de permanecer en la red es relevante. Además, el hecho de que el equipo se apague o no en la red
también depende de los ajustes de protección. Los ajustes de protección dominan la capacidad de resistencia a
las interferencias.
10.3.1 Dynamic grid support by way of immunity to interference
Interference immunity against undervoltage
Voltage drop above the limit curve in can be overcome without the need for shutdown from the grid. The feed-
in power remains constantly within the limits of the maximum continuous current of the inverter.
If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage
returning.
Página 68
Action in this menu/meaning
Only evaluated in mode 1.
0
The function is deactivated if the frequency returns to the range betwe-
en the minimum and maximum deactivation threshold and remains in
this range for the duration of the deactivation time.
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The li-
mitation is implemented by an absolute power limitation that increases
10 [% / min] /
with a continuous gradient up to the maximum power. The actual po-
wer of the inverter may vary freely below this limit due to a possible
fluctuation in the available power or the target value, but at no time in-
creases above the absolute power limit.
Dynamic gradient maximum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum char-
ging power if the frequency rises to the maximum configured frequency.
Dynamic gradient minimum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
0.01
to guarantee a linear power adjustment and reach the maximum feed-in
power if the frequency drops to the minimum configured frequency.
Establece el comportamiento dinámico al cambiar la potencia efectiva
para el aumento y la caída de potencia. En caso de cambio de tensión, la
potencia efectiva se modifica con el gradiente establecido.
Aviso: El gradiente se superpone al tiempo de ataque.
Manual
Kaco blueplanet 29.0TL3