Active Power Regulation - Kaco blueplanet 3.0 TL3 M2 WM OD IIG0 Manual

Hide thumbs Also See for blueplanet 3.0 TL3 M2 WM OD IIG0:
Table of Contents

Advertisement

Manual
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
1 – 60000 [% S
min]
Min. cos-phi Q1 - Min.
cos-phi Q4
Q1
Q4
Q2
Q3
Priority mode
Q priority | P priority
Active curve
1 – 4
Reset the curve
Number of nodes
2 – 10
1st node ... 10th node
0V - Max. voltage in
continuous operation
1 – 0.3
Over-excited | under-
excited
10.2

Active power regulation

10.2.1 P limit
The function "P limit" is available for limiting the maximum feed-in power. If necessary, this can be used to re-
duce the maximum possible feed of an inverter, e.g. for managing bottlenecks for the operator of the distribu-
tion grid.
P limit is only available via the MODBUS/SunSpec inverter model 123 Immediate Inverter Controls
and via RS485 communication. You can find detailed information on the communication protocol at
newenergy.de
in the "Software" subsection of the "Downloads" section.
When a target value is received for P limit, the output power of the inverter is limited to the specified power
value. If the limit value is changed, the new value is adopted by way of a filter and a gradient limitation. The
current power may be below the specified limit value because the available power (PV) or the target power
value (storage) may be below the specified limit value. Depending on the inverter series, the settling time and
gradient limitation may be adjustable.
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
In addition to configuring the dynamic behaviour using the transient
time corresponding to a first-order filter, the reactive power setting can
be determined by a maximum gradient - this means the maximum
change in the reactive power per time period.
/
Maximum change in the reactive power %S
max
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
In the event of a significant voltage deviation, the maximum reactive
power adjustment range can be limited by a minimum cos ϕ in order to
prevent an excessive reactive power supply and, as a result, a significant
reduction in the maximum active power that can be fed in.
Minimum cos ϕ in over-excited operating mode (in-feed).
Minimum cos ϕ in under-excited operating mode (in-feed).
Minimum cos ϕ in over-excited operating mode (charge).
Minimum cos ϕ in over-excited operating mode (charge).
P priority can be selected as an alternative to the standard setting Q pri-
ority. When it comes to P priority, the reactive power adjustment range
is limited subject to the limited apparent power of the inverter and the
active power that is currently available and fed in.
Up to four characteristic curves can be configured independently and
one of them can be activated for regulation each time.
Reset active curve to the factory setting, depending of the country set-
ting.
Specify the number of nodes for the Q(U) characteristic curve.
Voltage of the node in volts.
The voltage values of the nodes must increase continuously. At voltages
below the 1st node and voltages above the last node, the reactive
power value of the 1st or last node is used each time.
Reactive power of the node as a percentage of the maximum power
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Specifications | 10
Action in this menu/meaning
/min in the event of a
N
www.kaco-
Page 59

Advertisement

Table of Contents
loading

Table of Contents