Active Power Regulation - Kaco blueplanet 3.0TL3 Series Manual

Hide thumbs Also See for blueplanet 3.0TL3 Series:
Table of Contents

Advertisement

Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Priority mode
Q priority | P priority
Active curve
1 – 4
Reset the curve
Number of nodes
2 – 10
1st node ... 10th node
0V - Max. voltage in
continuous operation
1 – 0.3
Over-excited | under-
excited
10.2

Active power regulation

10.2.1 Active power limitation
The function "P target value" is integrated into the MPP tracking of the inverter on all PV inverters. The P target value is
continuously re-calculated on the basis of the MPP tracking algorithm.
P limit
The function "P limit" is available for limiting the maximum feed-in power. If necessary, this can be used to reduce the
feed of an inverter, e.g. for managing bottlenecks for the operator of the distribution grid.
P limit is only available via the MODBUS/SunSpec inverter model 123 WMaxLimPct and via RS485 communication. You
can find detailed information on the communication protocol at
the "Downloads" section.
When a target value is received for P limit, the output power of the inverter is limited to the specified power value. If the
limit value is changed, the new value is adopted by way of a filter and a gradient limitation. The current power may be be-
low the specified limit value because the available power (PV) or the target power value (storage) may be below the spe-
cified limit value. Depending on the inverter series, the settling time and gradient limitation may be adjustable.
Parameters
Power Limitation
[WMaxLimPct]
Timeout
[WMaxLimPct_RvrtTms]
Settling time
[VArPct_RmpTms]
Page 58
Action in this menu/meaning
P priority can be selected as an alternative to the standard setting Q pri-
ority. When it comes to P priority, the reactive power adjustment range
is limited subject to the limited apparent power of the inverter and the
active power that is currently available and fed in.
Up to four characteristic curves can be configured independently and
one of them can be activated for regulation each time.
Reset active curve to the factory setting, depending of the country set-
ting.
Specify the number of nodes for the Q(U) characteristic curve.
Voltage of the node in volts.
The voltage values of the nodes must increase continuously. At voltages
below the 1st node and voltages above the last node, the reactive
power value of the 1st or last node is used each time.
Reactive power of the node as a percentage of the maximum power
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Setting
0 – 100 [%]
3 – 100000 [%]
1000 [ms]
KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3
www.kaco-newenergy.de
Reference Description
Specifies the standard power in the event of a
communication failure. If no active power com-
mand is received within the configured timeout,
the inverter sets the power to the configured
fallback power.
Specifies the timeout time after which the in-
verter sets the fallback power in the event of a
communication failure.
Non-configurable settings 1 s.