Vertical Vent Termination - Valor H3 1000KN Installation Manual

Direct vent zero clearance gas fireplace
Hide thumbs Also See for H3 1000KN:
Table of Contents

Advertisement

Venting

Vertical Vent Termination

Minimum
Roof Pitch
"H" (feet)
Flat to 7/12
1'
Over 7/12 to
1.5'
8/12
Over 8/12 to
2'
9/12
Over 9/12 to
2.5'
10/12
Over 10/12 to
3.25'
11/12
Over 11/12 to
4'
12/12
Over 12/12 to
5'
14/12
f i r e - p a r t s . c o m
Horizontal
overhang
Termination
cap
Vertical
Min.
wall
18"
Storm
collar
Roof
flashing
Overhang should not
extend beyond vent if
within 48" of
termination cap
Min. 24"
(unvented soffit)
Min. 36"
(vented soffit)
'H'
Co-axial
27