Venting Chart - Valor H3 1000KN Installation Manual

Direct vent zero clearance gas fireplace
Hide thumbs Also See for H3 1000KN:
Table of Contents

Advertisement

Venting
How to Read the Venting Chart
The chart below applies to co-axial roof or wall
termination.
1. Maximum 18 inches horizontal pipe section
allowed with no vertical in vent system.
45 degrees elbow ok on horizontal plane.
2. The total length of the vent pipe cannot
exceed 40 feet.
3. The minimum vertical height with roof
termination
is 6 feet.
4. Any combination of rise and run can be
used as long as they are within the allowable
limits shown on the chart below.
5. A maximum of 4 x 90 degrees elbows—or
equivalent (2 x 45 degrees = 90 degrees)—
can be used.
f i r e - p a r t s . c o m
6. Each 90 degrees elbow installed on the
horizontal plane is equivalent to a 3 feet
horizontal pipe; therefore, 3 feet must be
subtracted from allowable horizontal run.
(45 degrees elbow is equivalent to 18 inches
horizontal pipe.)
7.
All horizontal pipe runs must be graded
1/4 inch per foot upwards in the direction
of the exhaust fl ow. The fi nal pipe length,
when terminating through the wall may be
graded downwards slightly to prevent water
migration.
8. A restrictor adjustment is required for most
installations having a vertical rise—see next
section.
Note: The restrictors are shipped loose with
the appliance.

Venting Chart

Allowable Co-Axial Vent Confi gurations
with restrictor positions
40
38
36
34
Position #5
32
30
28
26
24
22
Position #4
20
18
16
14
Example 1
12
10
8
6
4
2
0
2
4
HORIZONTAL RUN (ft)
No restrictor
Example 1
V Value = V1 (3') + V2 (2') + V3 (2')= 7'
H Value = H1 (3') + H2 (2') = 5'
Restrictor position #3 required
NO INSTALLATION
Position #3
Position #2
NO INSTALLATION
6
8
10
12
14
Co-axial
16
18
20
23