Installation

Connect Gas Supply

The gas supply inlet connection is a 3/8" NPT male con-
nector located on the right hand side of the fi rebox.
X
1-1/2"
[38 mm]
Gas line access—right side view
The unit is supplied with a stainless steel fl ex line to
allow the appliance to be disconnected for service. An
individual shut-off valve (not supplied) is required on
the supply line ahead of the fl ex connector.
Use only new black iron or steel pipes or copper tub-
ing if acceptable—check local codes. Note that in USA,
copper tubing must be internally tinned for protection
against sulfur compounds.
Unions in gas lines should be of ground joint type.
The gas supply line must be sized and installed to pro-
vide a supply of gas suffi cient to meet the maximum de-
mand of the appliance without undue loss of pressure.
Sealant used must be resistant to the action of all gas
constituents including LP gas. Sealant should be applied
lightly to male threads to ensure excess sealant does
not enter gas lines.
42
"
/ 1 6
]
3 - 5
m m
[ 8 5
Gas line access hole
1-1/2" [38 mm] diam.
Pressure test the supply line for leaks.
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply pip-
ing system at test pressures equal to or less than 1/2
psig (3.5 kPa).
Failure to either disconnect or isolate the appliance
during pressure testing may result in regulator or valve
damages and void the warranty. Consult your dealer in
case of damages.