Step 2:
Set I/O module to the initial state
If the module is a new one, factory have set a default settings for user's convenient. If you use
an old one and you don't know the configuration of the module, please set the I/O module to
the initial state.
*** To set I-7000 module to the initial state, please wire the INIT* to GND and power on the
module. Then the module will become initial state.
*** I-87K module's initial state is set by the DIP switch of Expansion Unit (e.g. I-87Kn). For
example, setting DIP-2 to "ON", and then re-cycle the power, it means the second slot is in
initial state.
The default state from factory:
I/O Module
Address
Baud rate
Checksum
Protocol
The initial state after initiation:
I/O Module
Address
Baud rate
Checksum
Protocol
Step 3:
Select COM Port and Baud rate to search
Execute the [ DCON Utility ] :
1. Click "COM Port" menu to select the COM port and Baud rate to search. Select multi-baud
rate, protocol or checksum conditions if you do not know the module's setting, but it will
spend more time to scan the network. After selection, click "OK".
2. Click
Getting Started: PAC-7186EG(D) & I-7188EG(D)/XG(D), Jul 2020 V4.0
I-7000
1
9600
Disabled
DCON Protocol
(I-7000 and M-7000)
"Start Search" icon to begin search module. Click
M-7000
1
9600
Not defined
Modbus Protocol
7000 series
0
9600
Disabled
DCON Protocol
87K series
1
115200
Disabled
DCON Protocol
87K series
0
115200
Disabled
DCON Protocol
when it is searched.
71
.