Bentone BF 1 FUV FAME/RME Installation And Maintenance Instruction page 29

Table of Contents

Advertisement

6.1.3 Filter replacement
Cut off the power and shut off the oil.
Remove the pump cover with the aid of a 4 mm Allen key. If necessary a
screwdriver may be used between the cover and the housing to carefully
pry the cover loose. Replace the old fi lter by a new one. Replace the cover,
tighten lightly.
Do not forget to replace the gasket.
Open the oil supply and switch on the power.
9
1
6.1.4 One-pipe system
2
3
Conversion to one-pipe system
Remove the return plug (8), plug the return
line (9) with the metal plug (7) G 1/4".
6.1.5 Two-pipe system
Conversion to two-pipe system
Remove the metal plug (7) G ¼", fi t the
return plug (8) in the return line (9).
Return plug are not included in products
8
with one-pipe system, separately sold.
5
4
7
6
6.1.6 Solenoid valve