178 111 35-4 P93783 2023-01-16 Providing sustainable energy solutions worldwide Installation- and maintenance instruction BFG 1 H2 Biogas LME23.331C2 DMV-DLE 507 FRS 510 VPS 504 Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\ nedladdning eller scanna or scan QR-code. download eller scan QR-koden.
Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 172 515 01-2 2021-10-05 Bentone...
Prevent open fl ames or sparking, e.g. do not turn lights on or off, do • not use any electrical appliances or mobile phones. • Evacuate the building. Notify the installer or gas supplier of the problem so that it can be • rectifi ed. Bentone...
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air intake to the air duct that opens into an appropriate location. Installation must be done so it does not prevent air supply to the burner. Bentone BFG 1...
Model BFG 1 H2 3-3.5 2.5.1 Burner output/Basic settings 15-50 kW mbar Do not exceed working field. -0,5 Air settings Scale Nozzle assembly Scale value valid at 0 mbar in furnace pressure. Burner output Bentone BFG 1...
Components Flame tube Connection gas valve Gas pressure switch Gas valve Pressure regulator Filter Ball valve Ignition transformer Capacitor Motor Bentone BFG 1...
Page 10
Leakage control (VPS) Nozzle assembly adjustment Screw for dividing the burner Electric connection Air fl ow indicator Air intake Air regulation Nozzle assembly Air pressure switch Brake plate Gas burner control Ignition electrodes Reset button Nozzle Bentone BFG 1...
Connection must be done in accordance with the applicable • regulations. • Connection must conform to the wiring diagram. If any electrical connection other than that recommended by Enertech is used, there is a risk of property damage and personal injury. 172 535 09-2 Bentone...
Electric equipment Safety system The safety system (safety switch for hatches, doors, water level, pressure, temperature and other safety devices) must be installed in the safety circuit in accordance with current regulations for the system. If these safety requirements are met by other means, safety circuits must be bypassed/jumpered.
4.2.1 List of components Gas burner control Temperature limiter Leakage control VPS 504 Main switch Ionisation electrode Air pressure switch UV-detector QRC Gas pressure switch, min Fuse Ignition Transformer Operating lamp Solenoid valve Motor Plug-in contact, burner Timer total operating time Plug-in contact, boiler Control thermostat Function LME...
Control program at faults; fault mode indicator LME ..4.4.1 Colour codes Table colour codes for multi-coloured signal light (LED) Status Colour codes Colours ○………………… Waiting period «tw», other waiting periods ●○●○●○●○●○● Blinking yellow Ignition phase, ignition controlled □………………… Normal operation Green □○□○□○□○□○...
Page 16
4.4.1.3 Alarm code table Red blinking code on Possible causes signal lamp (LED) Blinking 2 x No flame creation at End of “TSA” – defective or fouled flame monitoring. •• – defective or fouled fuel valves. – poor burner setting. –...
X2 according to the wiring diagram. Turn off the main switch. Connect the Eurostecker X2 acc. to Alt. 1 - 3, (see Electric equipment). Install the Eurostecker X2 on the burner. Turn on the main switch. 172 525 26-2 Bentone BFG 1...
1.5 x max inlet pressure or min. 150 mbar. If leaks are found during measurement, locate the source using soapy water or leak detection spray. After sealing: check the tightness of the gas fixture again. Check the gas tightness. Bentone BFG 1...
Natural gas 34.02 32.25 116.09 Butane Natural gas 29.25 24.44 88.00 Propane Lower calorific value H at normal conditions 15 °C and 1013 mbar, EN 676. For exact calorific value of the gas, contact the gas distributor. 172 535 47 Bentone...
Fig. I, a clockwise turn gives a decrease in the air flow and a counter-clockwise turn an increase in the air flow. If the air intake is pointing upwards as in Fig. II, a clockwise adjustment increases the air flow and a counter-clockwise adjustment decreases the air flow. 172 525 27-2 Bentone BFG 1...
Page 21
A hose connection via a air duct is available in three different dimensions, 48, 68 and 78 mm outer diameter ”D”. The air duct is installed on the air intake at the place where the grid is installed in the standard design. Bentone BFG 1...
Measure and note the lowest air pressure in the entire work area. Set the air pressure switch to about 10-15% lower than the lowest noted pressure. Test run the burner and check the function in the entire work area. Refi t protective cover. 172 535 11-2 Bentone...
When the gas pressure switch stops the burner, the measured value must approximately correspond to the setting on the gas pressure switch. Open ball valve. Remove manometer and close measuring socket. Refi t protective cover. Check gas tightness. 172 535 12-2 Bentone...
The red LED is lit as long as the contact is released by the regulator (heat requirement). After a short voltage drop during testing or during burner operation, an automatic restart is performed. Pressure buildup Operation Programmer Idle state 172 615 10 2018-01-15 Bentone...
Release signal Fault signal Electrical connection The VPS 504 is connected in series between the temperature regulator and the control box via a 7-pin plug connector. See wiring diagram! Tight Untight Lock-out Operation Outlet Operating voltage ~(AC) 230V 50Hz Bentone...
Max. operating pressure 500 mbar Class A Pressure regulator -15 °C … +70 °C Ambient temperature 5 - 500 mbar Inlet pressure range 1 + 2 + 3 Family Outlet pressure range 2,5 - 200 mbar 172 515 66 2018-01-02 Bentone...
Page 28
Turn spindle to stop. Unscrew complete adjustment device B and remove spring C. Insert new spring D. Assemble complete adjustment device and adjust desired off-set. Screw on protective cap A. Stick adhesive label E onto typeplate. Attach lead seal. Bentone...
Max. operating pressure 500 mbar DMV 505-520/11 Pressure taps 1, 2, 3, 4 Sealing plug Screw plugs 1,2,3 may also be replaced by a measuring socket G 1/8 DIN ISO 228. Concealed connecting bore for system accessories. 172 515 67 2018-02-12 Bentone...
Page 30
1 - 5. Switch on firing system. Replace solenoid Important: Make sure that the solenoid no. and voltage are correct! Remount hydraulic brake or adjust-ing plate as described on page 6. ”Replacing the hydraulic brake or adjusting plate”, steps 7 -11. Bentone...
Replacement upon fault detection 10 years 250,000 starts Gas pressure switch Safety blow-off system 10 years 500,000 starts Damper motor Contactor 10 years 500,000 starts The burner and its components must be recycled according to applicable regulations. 172 615 88-2 2022-09-08 Bentone...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 15-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 16-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 17-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 18-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which aff ect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 19-2 Bentone BFG 1...
Page 37
When the ignigtion transformer, air switch, gas switch and gas burner control contained in the electrical package are being replaced, no work needs to be done in the socket. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. Bentone BFG 1...
Min. DC 3 µA Required current to ensure detection Max. DC 20 µA Possible detection current Operational indicator lamp flashes green <5 µA DC Operational indicator lamp shines green >5 µA DC 10.8.1 Flame monitoring ionisation 172 615 02-3 Bentone...
Page 39
Max. current for flame detection Max. DC 5.5 µA Min. DC 40 µA Required current to ensure detection Max. DC 60 µA Possible detection current Operational indicator lamp flashes green <45 µA DC Operational indicator lamp shines green >45 µA DC Bentone...
Instruct the persons in charge of the operation on the service and • maintenance of the installation and what to do should any troubles occur. Inspection and service must be carried out by authorized personnel. • Review and service should be performed by authorised personnel only. 172 615 04-2 Bentone...
Voltage lower than 185V. Contact an electrician. Ignition electrodes disrupting ionisation current. Adjust ignition electrodes. Re-polarise the transformer. Poor earth connection. Ensure adequate earth connection. Phase and neutral swapped around. Check wiring diagram and change accordingly. 172 615 06 2018-01-10 Bentone...
Page 42
Flame at incorrect angle due to combustion head out of position. Condensation build up in boiler and chimney: Flue gas temperature too low or gas volume too low. Raise the flue gas temperature by increasing gas volume Insulate the chimney. Bentone...
13. Service- and inspection protocol Installation Boiler Efficiency kW: Name: Type: Address: Burner Efficiency kW: Type: Installed by: Date: Date gas/h Efficiency Governor Fluegas Ionisation Pressure temp current Fire Chimney room Measure- °C µ A ment Before After mbar mbar Small Flame Large Flame...