Bentone BF 1 FUV FAME/RME Installation And Maintenance Instruction page 22

Table of Contents

Advertisement

5.1.4
Replacing the oil pump
1.
Break the main current and disconnect the Euro plug from the burner.
2.
Disconnect the electrical plug from the oil valve (1).
3.
Detach the oil hoses from the pump.
4.
Detach the solenoid valve housing from the valve (2). Remove the
entire solenoid valve housing.
5.
Disconnect the oil connection pipes from the solenoid valve (3).
6.
Loosen the screws (4) and pull out the oil pump and solenoid valve as
one assembly.
7.
Turn the valve forward and detach it from the pump.
8.
Reassemble in reverse order.
!
Do not forget thread
sealer between the pump
and the elbow.
(t.ex Loctite 5188, 5400)
4
!
When servicing or replacing components that affect combustion, analyses and
soot tests must be carried out on the installation.
22
Bentone
2
fi g 1
1
3

Advertisement

Table of Contents
loading