2.3.2 Basic settings - Fuel oil
Scale
22,0
20,0
18,0
16,0
14,0
12,0
10,0
8,0
6,0
4,0
2,0
0,0
15
20
25
2.3.3 Basic settings - HVO/XTL
Scale
22,0
20,0
18,0
16,0
14,0
12,0
10,0
8,0
6,0
4,0
2,0
0,0
15
20
25
Flame signal
When operating at high power or low air excess and HVO/XTL is used as
fuel, the flame signal may deteriorate (blue flame), the signal lamp in the
reset button flashes green.
By lowering the air velocity or changing the flame detector to QRC1 A1,
the flame signal can be improved.
10
Bentone
Air settings
Nozzle assembly
30
35
40
45
Air settings
Nozzle assembly
30
35
40
45
!
Scale value applies
to 0 mbar furnace
pressure.
kW
50
55
Burner output
!
Scale value applies
to 0 mbar furnace
pressure.
kW
50
55
Burner output