Vega POINTRAC 31 Operating Instructions Manual page 16

Radiometric sensor for level detection
Table of Contents

Advertisement

4 Mounting
Mounting clamp
16
3
2
1
Fig. 5: Mounting position - level detection - version without detector tube
1
Horizontal mounting
2
Vertical mounting
3
Mounting horizontally, at right angles to container
You can find information on protective barriers and the mounting
of the corresponding source container in the operating instructions
manual of the source container, e.g. VEGASOURCE.
For level detection, the device is generally mounted horizontally at the
height of the requested limit level. Make sure that there are no struts
or reinforcements at this position in the vessel.
Direct the exit beam of the source container exactly towards the
measuring range of POINTRAC 31.
Fasten the devices in such a way that it cannot fall out of the holder. If
necessary, provide the device with a support from below.
Mount the source container as close as possible to the vessel. If there
are gaps, secure the area with a safety fence and protective grating
so that no one can reach into the dangerous area.
You can mount the device (version with detector tube) with the at-
tached mounting clamp to your vessel.
POINTRAC 31 • Foundation Fieldbus

Advertisement

Table of Contents
loading

Table of Contents