Burnout Detection
The Burnout Detection function, or open-wired function, is designed for 4~20mA
input range or temperature input range. For the WISE-4671, the burnout signal is
activated when the current is less than 3mA. The Modbus flag indicates that the wire
of the sensor connected to the channel has burned out. You can also check the Mod-
bus address of AI Channel Status for detail. When a burnout situation had been
detected, the AI value can be shown in "Up scale" which is FFFF(HEX), or "Down
scale" which is 0. You can configure this in "Burnout Detection Mode".
Sampling Rate
For models which support more than one sampling rate, you can configure the sam-
pling rate here. For low sampling rate mode, the AI channel would have better noise
rejection ability. For the high sampling rate mode, the noise will allow easier coupling
to the signal.