AIR REGULATION ON THE COMBUSTION HEAD

The combustion head is equipped with a regulation device that
makes it possible to open or close the air passage between the
disk and the head. Closing the passage increases the pressure
upstream of the disk also with low flow rates. The high speed and
turbulence of the air provides for its greater penetration into the
fuel and therefore an excellent mixture and flame stability. High air
pressure upstream of the disk may be necessary to prevent flame
fluctuations, this is particularly essential when the burner works
on the furnace that is pressurised and/or at a high thermal load.
CAUTION / WARNINGS
Check that the combustion head is centred with respect
to the disk. An imperfect centring could cause a poor
combustion and overheating of the head with its subsequent
rapid deterioration.
CAUTION / WARNINGS
The above adjustments are only indicative; position the
combustion head according to the characteristics of the
furnace.
BURNER
TBG 80 LX P
10 ÷ 25
TBG 110 LX P
15 ÷ 25
TBG 140 LX P
10 ÷ 46
TBG 200 LX P
14 ÷ 51
• Loosen the screw (1)
• Turn screw (2) to position the combustion head (3), referring to
index (4)
• Adjust the distance (x) between the minimum and maximum
according to the indications in the table
Value indicated by
X
index 4
1 ÷ 2,8
1 ÷ 2.2
1 ÷ 5
1 ÷ 5
0006160250_201803
19 / 34