Sungrow SG5KTL-MT User Manual page 65

Pv grid-connected inverter
Hide thumbs Also See for SG5KTL-MT:
Table of Contents

Advertisement

User Manual
D D e e s s c c r r i i p p t t i i o o n n
A A l l a a r r m m I I D D
Grid low voltage
The grid voltage is
005
below the specified
protection value, lower
than grid undervoltage
AC instantaneous
overcurrent
007
AC output current
exceeds the upper limit
of the inverter.
Grid overfrequency
Grid frequency
008
exceeds the upper limit
of the inverter.
Grid underfrequency
Grid frequency is below
009
the lower limit of the
inverter.
No Grid
AC switch or circuit
010
breaker is
disconnected.
9 Troubleshooting and Maintenance
C C o o r r r r e e c c t t i i v v e e M M e e a a s s u u r r e e s s
Generally, the inverter will be reconnected to
the grid after the grid recovers. If the alarm
occurs frequently:
1. Measure the grid voltage, and contact the
local utility grid company for solutions if the
grid voltage is below the specified value.
2. Check, through the App, whether the
protection parameters are appropriately set.
3. Check whether the AC cable is firmly in
place.
4. If the alarm persists, contact SUNGROW.
Generally, the inverter will be reconnected to
the grid after the grid recovers. If the alarm
occurs frequently, contact SUNGROW.
Generally, the inverter will be reconnected to
the grid after the grid recovers. If the alarm
occurs frequently:
1. Measure the grid frequency, and contact the
local utility grid company for solutions if the
grid frequency is beyond the specified range.
2. Check, through the App, whether the
protection parameters are appropriately set.
3. If the alarm persists, contact SUNGROW.
Generally, the inverter will be reconnected to
the grid after the grid recovers. If the alarm
occurs frequently:
1. Check whether the grid supplies power
reliably.
2. Check whether the AC cable is firmly in
place.
3. Check whether the AC cable is correctly
connected (whether the live wire and the N
wire are in correct place).
4. Check whether the AC switch or circuit
breaker is disconnected.
5. If the alarm persists, contact SUNGROW.