All the AC cables should be equipped with correctly colored cables for distinguishing.
Please refer to related standards about the wiring color.

5.4.2 Assembling the AC Connector

The AC terminal block is on the bottom of the inverter. AC connection is the three-
phase-four-wire grid +PE connection (L1, L2, L3, N, and PE).
step 1 Unscrew the waterproof terminal of the AC connector counter clockwise.
step 2 ( ( O O p p t t i i o o n n a a l l ) ) Remove the inner rubber gasket if the external diameter of the to-be-used
AC cable ranges from 19~25mm.
step 3 Thread the AC cable of appropriate length through the waterproof terminal.
step 4 Remove the cable jacket by 80~90 mm, and strip the wire insulation by 12 mm.